| 2020-08-14 11:33:24 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | A- PROPOSED REVISIONS TO APPROVED PLANS |
| | |
| | 1) REVISED SHEETS A111A&B, A121A&B, A181A&B HAVE THE |
| | MECHANICAL DUCTS AND OTHER MECHANICAL INFORMATION ON |
| | THEM. THESE ARE ARCHITECTURAL FLOOR PLANS. REVISED PLAN |
| | SHEETS REPLACE THE ORIGINALS, THEREFORE THESE SHEETS |
| | CAN NOT BE APPROVED BECAUSE REQUIRED FLOOR PLAN |
| | INFORMATION IS OBSCURED BY THE MECHANICAL ITEM OVERLAY. |
| | YOU WILL NEED TO REVISE THE APPROPRIATE MECAHNICAL |
| | DRAWINGS OR SUBMIT THESE PLANS AS NEW SHEETS WITH |
| | DIFFERENT SHEET NUMBERS AND MECHANICAL LABELS. CITY |
| | AMENDMENTS FBC 107.2.1.3 |
| | |
| | 2) THE PLANS DO NOT HAVE THE ENGINEER'S OR ARCHITECT'S |
| | DIGITAL SIGNATURE AS REQUIRED BY FS 471 AND 481. SEE |
| | THE SIGNATURE REVIEW STOP. |
| | |
| | SHOP DRAWINGS: |
| | |
| | B - STRUCTURAL STEEL CALCULATIONS |
| | |
| | 1) THE ELECTRONICALLY SUBMITTED STEEL FRAMING |
| | CALCULATIONS ARE REQUIRED TO HAVE (DEWEY A. LEBANC |
| | P.E.) THE ENGINEER'S DIGITAL SIGNATURE. I WAS UNABLE TO |
| | VERIFY THE SIGNATURE. FS 471 & FAC 61G-15 SEE THE |
| | SIGNATURE REVIEW STOP. |
| | |
| | 2) THE STEEL FRAMING CALCULATIONS ARE REQUIRED TO BE |
| | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| | (ARCHITECT/ENGINEER OR BOTH) IN RESPONSIBLE CHARGE. |
| | CITY AMENDMENTS FBC107.3.4.1 |
| | |
| | 3) PARTS OF THE STEEL FRAMING CALCULATIONS ARE NOT |
| | LEGIBLE. CITY AMENDMENTS FBC 107.2.1 |
| | |
| | C - STEEL TRUSSES |
| | |
| | 1) THE ELECTRONICALLY SUBMITTED STEEL TRUSS DRAWINGS |
| | ARE REQUIRED TO HAVE THE TRUSS ENGINEER'S DIGITAL |
| | SIGNATURE. FS 471 & FAC 61G-15 SEE THE SIGNATURE REVIEW |
| | STOP. |
| | |
| | 2) THE STEEL TRUSS DRAWINGS ARE REQUIRED TO BE REVIEWED |
| | FOR CONFORMANCE WITH THE DESIGN OF THE BUILDING BY THE |
| | DESIGNER OF RECORD (ARCHITECT/ENGINEER OR BOTH) IN |
| | RESPONSIBLE CHARGE. CITY AMENDMENTS FBC107.3.4.1 |
| | |
| | 3) THE TRUSS PLACEMENT PLANS HAS AN ADDRESS OF 901 S |
| | FLAGLER. THE ADDRESS OF THIS PROJECT IS 351 PEMBROKE |
| | PLACE. CITY AMENDMENTS FBC 107.2.1.3 |
| | |
| | |
| | |
| | |
| | |