| Plan Review Notes For Permit 20071273 |
| Permit Number |
20071273 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-10 09:52:08 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SCOPE OF WORK SHOWN ON YOUR DRAWING IS A LEVEL 2 | | | ALTERATION PER FBC EXISTING BUILDING. PLEASE NOTE THIS | | | ON THE PLANS. | | | | | | 2) PROVIDE DETAILS/WALL SECTION FOR THE KITCHEN WINDOW | | | INFILL. SPECIFY THE DIMENSIONS OF THE ROUGH OPENING. | | | SHOW ALL CONSTRUCTION MATERIALS AND INSULATION. SPECIFY | | | THE WIND LOAD DATA ON THE PLANS. WINDSPEED AND EXPOSURE | | | CATEGORY. FBC 107.2.1 | | | | | | 3) PROVIDE INTERIOR WALL FRAMING AND FINISH DETAILS. | | | FBC 107.2.1 | | | | | | 4) SUBMIT AN EXISTING FLOOR PLAN FOR THIS PROJECT. FBC | | | 107.2.1 | | | | | | 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 6) IT APPEARS THAT THE KITCHEN CABINETS ARE BEING | | | RECONFIGURED OR MORE CABINETS ARE BEING ADDED. | | | ADDITIONAL COUNTER TOP SPACE MAY REQUIRE ADDITIONAL | | | RECEPTACLES AND AN ELECTRICAL PERMIT AND ELECTRICAL | | | PLANS. | | | | | | 7) TO AVOID ADDITIONAL REVIEW COMMENTS AND PROVIDE | | | CLARIFICATION, IT MAY BE HELPFUL TO PROVIDE A NARRATIVE | | | LETTER EXPLAINING HOW EACH COMMENT HAS BEEN ADDRESSED. | | | | | | |
|