| Date |
Text |
| 2020-08-19 10:00:11 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20071234 |
| | ADD: 3950 GEORGIA AVE. |
| | CONT: BUILTMORE CONTRACTING |
| | TEL: 561-331-1476 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 19TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE TITLEBLOCK INDICATES THE PROPOSED WORK IS TO BE |
| | A BEER GARDEN. PLEASE NOTE THE OCCUPANTS AT 3950 |
| | GEORGIA DIDN?T APPLY FOR THEIR BUSINESS TAX LICENSE |
| | (OLD OCCUPATIONAL TAX) AS A BEER GARDEN, BUT AS TROY?S |
| | BARBEQUE AS OF 08/05/2020? YOU MAY WANT TO CONTACT YOUR |
| | CLIENT TO SEE WHAT ADDITIONAL WORK WILL BE INVOLVED. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. IT WOULD |
| | APPEAR THAT WITH BARBEQUED MEET WHERE IS THE COOKER, |
| | INSIDE OR OUT? IS A HOOD AND ANSUL SYSTEM REQUIRED? |
| | |
| | 2) THE DESIGNER OF RECORD HAS NOT INDICATED THIS IS A |
| | CHANGE OF OCCUPANCY AND WILL NEED TO SHOW AS SUCH ON |
| | THE PLANS. 2017 EXISTING BUILDING CODE METHOD OF PLAN |
| | DEVELOPMENT. 2017 EXISTING BUILD. CODE SECTION 301.1. |
| | THE REPAIRS, ALTERATIONS, CHANGE OF OCCUPANCY, |
| | ADDITIONS OR RELOCATION OF ALL EXISTING BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS |
| | 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE DESIGNER OF |
| | RECORD. IN THE CITIES RECORDS THE LAST PREVIOUS TENANT |
| | WAS A PAINT AND BODY SHOP, F1 OCCUPANCY. |
| | |
| | 3) PLEASE REVIEW IN THE 2017 FL. EXISTING BUILDING CODE |
| | SECTION 1001.2.2. CHANGE IN OCCUPANCY CLASSIFICATION. |
| | |
| | 4) ON SHEET A-1 THERE IS A NOTE THAT STATES ACCESSIBLE |
| | SERVICE IS AT TABLES, THERE IS NO SEATING AT THE BAR |
| | COUNTER. PLEASE BE AWARE THIS STATEMENT DISCRIMINATES |
| | AGAINST THOSE PATROONS IN WHEELCHAIRS. |
| | 2017 FL. ACCESSIBILITY CODE. 902.1 .DINING SURFACES |
| | SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 |
| | GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED |
| | TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | |
| | 4)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 4)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 5) PLEASE ALSO NOTE THE COUNTER TOP FOR THE REGISTER |
| | ALSO NEEDS TO BE COMPLIANT WITH CHECK WRITING SURFACES. |
| | 2017 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE |
| | PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH |
| | 902.3. 902.3HEIGHT. |
| | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION. |
| | UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE |
| | SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL |
| | APPROACH TO AN ELEMENT. |
| | 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND |
| | SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. |
| | THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND |
| | THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. |
| | |
| | 6) SHEET A-1 DOES NOT SHOW RESTROOM FACILITIES, PLEASE |
| | SHOW HOW COMPLIANCE WITH THE 2017 EXISTING BUILDING |
| | CODE SECTION 1010.6 SEPARATE FACILITIES WILL BE |
| | ACHIEVED. THIS CODE SECTION ALSO REFERS YOU BACK TO |
| | SECTION 810.2 EXISTING BUILDING CODE. |
| | |
| | 7) THE VALUE OF WORK FOR THE PERMIT SEEMS LOW, AND WITH |
| | COMPLYING WITH THE COMMENTS THE VALUE OF THE PROJECT |
| | WILL INCREASE. PLEASE ALSO BE AWARE OF THE |
| | ACCESSIBILITY CODE REQUIREMENTS OF DISPROPORTIONATE |
| | COST. |
| | DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU |
| | ARE TO MEET DISPROPORTIONATE COST. EITHER THE |
| | CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR |
| | LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP |
| | TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH |
| | ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE |
| | ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST |
| | OF THE 2017 ACCESSIBILITY CODE. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |