| 2020-08-12 10:55:51 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20071220 |
| | 8/11/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1 & P2 SANITARY ISOMETRIC: A) THE WATER |
| | CLOSET (P-1) AT WOMEN 111 IS NOT BEING VENTED BECAUSE |
| | IT IS NOT CONNECTING DIRECTLY INTO THE HORIZONTAL WET |
| | VENTED BRANCH LINE SERVING P-3 AND THE FD. AN |
| | INDIVIDUAL VENT IS REQUIRED IF IT IS TO BE CONNECTED |
| | DIRECTLY INTO THE MAIN DRAIN. B) THE HORIZONTAL WET |
| | VENTED SYSTEM SERVING WOMEN 112 APPEARS TO BE |
| | NON-COMPLIANT BECAUSE THE DRAIN LINES FOR P-3 AND THE |
| | LOWER P-1 ARE EACH CONNECTING VERTICALLY INTO THE |
| | BRANCH DRAIN LINE AND HORIZONTAL CONNECTIONS ARE |
| | REQUIRED- SECTIONS 912.1, 912.2 & 912.2.1 FBC P. C) |
| | IDENTIFY THE FIXTURE NEXT TO THE ICE MAKER. |
| | |
| | 2) P1: THE MAKE, MODEL AND CAPACITY OF THE EXISTING |
| | GREASE INTERCEPTOR MUST BE NOTED ON THE PLANS- SECTIONS |
| | 1003.3.4 AND 1003.3.6. THE PLAN SHOWS NEW FLOOR SINKS |
| | BELOW FOOD AND BEVERAGE PREP COUNTERS, |
| | THREE-COMPARTMENT SINKS, AND ALSO IN THE CENTER OF THE |
| | COMMERCIAL KITCHEN BELOW THE STEAM TABLE ALL OF WHICH |
| | ARE DRAINING INTO THE SANITARY INSTEAD OF THE GREASY |
| | WASTE LINE. PLEASE REFER TO SECTION 1003.3.1 REVISE THE |
| | PLANS AND SIZING CALCULATIONS ACCORDINGLY. |
| | |
| | 3) P-2: SUBMIT PRODUCT SPECIFICATION SHEETS FOR THE |
| | WATER HEATERS, AND EQUIPMENT SCHEDULES THAT INCLUDE THE |
| | EFFICIENCY RATINGS OF THE UNITS- SECTION C404.22 FBC |
| | EC. REFER TO TABLE 604.3 AND PROVIDE CALCULATIONS TO |
| | VERIFY THE EXISTING WATER HEATER SERVING THE PLUMBING |
| | FIXTURES IN THE KITCHEN AND BAR AREA HAS THE REQUIRED |
| | CAPACITY. |
| | |
| | 4) P-2: PROVIDE A PLUMBING DEVICE SCHEDULE THAT |
| | INCLUDES THE BACKFLOW PREVENTERS AND WATER HAMMER |
| | ARRESTORS- SEE SECTION 604.9 & TABLE 608.1. |
| | |
| | 5) SHEET 3.3: THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET IN THE MEN'S TOILET 106 COMPARTMENT SHALL BE 60 |
| | INCHES WIDE MINIMUM MEASURED PERPENDICULAR TO THE SIDE |
| | WALL, AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED |
| | WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL |
| | SECTION 604.8.1.1 FBC ACC. |
| | |
| | 6) 3.3: SHOW THE REQUIRED TURNING SPACES IN THE TOILET |
| | ROOMS AND COMPARTMENT- SECTION 304.3 AND FIGURE |
| | 604.8.1.6 |
| | |
| | 7) 3.3: KNEE AND TOE CLEARANCES FOR THE LAVATORIES ARE |
| | NOT SHOWN- SECTION 306. |
| | |
| | 8) 3.3: THE REAR GRAB BEHIND THE WATER CLOSET SHALL BE |
| | POSITIONED IN COMPLIANCE WITH FIGURE 604.5.2. |
| | |
| | 9) 3.3: THE HEIGHT OF THE GRAB BARS SHALL BE 33 INCHES |
| | MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE PLAN |
| | SHOWS THE MEASUREMENT TO THE CENTERLINE OF THE BARS- |
| | SECTION 609.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |