Plan Review Notes
Plan Review Notes For Permit 20071211
Permit Number 20071211
Review Stop B
Sequence Number 2
Notes
Date Text
2020-09-29 16:25:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20071211
 ADD: 371 MACY ST.
 CONT: UNLIMITED WINDOWS & DOORS
 TEL: 561-318-7105
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SEPT. 29TH/ 2020
 ACTION: DENIED
  
 1) COMPLIED/ CONTRACTOR.
  
 2) COMPLIED. CONTRACT VALUE $4265.00 + $2700 LABOR TO
 INSTALL= $ 6967.00. .
  
 3) 2ND REQUEST. AS A CONTRACTOR CAN CERTIFY THEIR OWN
 PLAN THEY TAKE ON THE RESPONSIBILITY OF THAT PLAN
 SIGNING THEIR NAME TO THE PLAN, AND THEN PRINTING THEIR
 NAME ON THE PLAN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE
 INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING,
 ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE
 TRADES UNDER ONE SHEET.
  
 4A) THE SUBMITTED MIAMI-DADE NOA 18-0129.08 FOR
 MULLIONS DOES NOT IDENTIFY WHICH TYPE OF MULLION THAT
 IS GOING TO BE INSTALLED AND TRIBUTARY AREA THE MULLION
 IS GOING TO TAKE THE LOAD OF AND PRESSURES.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO THE BUILDING DEPARTMENT. FOR ALL MULLIONS
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURERS INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
 4B) THE REPORT FOR SERIES 4100A IMPACT SINGLE HUNG
 WINDOWS DOES NOT INDICATE EITHER A FLORIDA APPROVAL NOR
 MIAMI-DADE NOA. ALL TESTING REPORTS, ALL TESTING
 REPORTS MUST HAVE 3RD PARTY CERTIFICATION FL.
 ADMINISTRATIVE RULE 61G20-3.005. EVEN IF APPLIED FOR A
 LOCAL APPROVAL WE STILL HAVE THE SAME REQUIREMENTS AS
 THE STATE.
 5) THE ENGINEERING SHEET LOOKS LIKE IT MAYBE A PAPER
 ORIGINAL THAT HAS BEEN UPLOADED TO PROJECT DOX.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  