| Date |
Text |
| 2020-08-02 16:49:44 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20071211 |
| | ADD: 371 MACY ST. |
| | CONT: O/B (OWNER BUILDER) MATHEW CARY |
| | TEL: 561-654-0009 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUNDAY AUGUST 02ND/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE OWNER IS TAKING EXCEPTION TO THE CONTRACTING |
| | LAWS AND MUST FILE OUT A OWNER/ BUILDER FORM BEFORE |
| | RESUBMITTING TO THE BUILDING DEPARTMENT. FORMS CAN BE |
| | FOUND ON LINE. |
| | |
| | 2) THE STATED VALUE IS TO BE FOR THE VALUE OF THE |
| | WINDOWS, LABOR AND HAULING AWAY OF ANY TRASH. THE VALUE |
| | SEAMS LOW ON LABOR. LABOR IS USUALLY EQUAL TO THE COST |
| | OF THE WINDOWS. THE CALCULATED VALUE IS $8,702.00 |
| | DOLLARS. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 109.3* |
| | BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 3) AS PERMITTING BY OWNER BUILDER YOU ARE TAKING |
| | RESPONSIBILITY FOR THE FLOOR PLAN YOU DREW. JUST AS A |
| | CONTRACTOR CAN CERTIFY THEIR OWN PLAN THE OWNER BUILDER |
| | MUST ALSO TAKE THAT SAME RESPONSIBILITY BY SIGNING |
| | THEIR NAME TO THE PLAN, AND THEN PRINTING THEIR NAME ON |
| | THE PLAN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR |
| | RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN |
| | MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE |
| | NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE |
| | INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING, |
| | ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE |
| | TRADES UNDER ONE SHEET. |
| | |
| | 4) THE SUBMITTED MIAMI-DADE NOA 18-0129.08 FOR MULLIONS |
| | DOES NOT IDENTIFY WHICH TYPE OF MULLION THAT IS GOING |
| | TO BE INSTALLED AND TRIBUTARY AREA THE MULLION IS GOING |
| | TO TAKE THE LOAD OF AND PRESSURES. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO THE BUILDING DEPARTMENT. FOR ALL MULLIONS |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 5) THE 2 ENGINEERING SHEETS LISTED AS 4100A & 4120AARE |
| | DEFINITELY NOT A MIAMI-DADE NOA AND APPEAR NOT TO BE A |
| | FLORIDA APPROVAL SINCE THERE IS NO LISTING NUMBER. |
| | PLEASE NOTE FOR EITHER MIAMI-DADE NOA.S, FLORIDA |
| | APPROVALS AND ALL OTHER APPROVALS WITH THE STATE OF |
| | FLORIDA, THE PRODUCTS MUST HAVE THIRD PARTY |
| | CERTIFICATION. THE CITY REQUIRES THE SAME 10 |
| | REQUIREMENTS FOR A LOCAL APPROVAL AS REQUIRED BY THE |
| | STATE. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3. |
| | |
| | 6) AS OWNER BUILDER YOU CAN FIND THE WIND DESIGN |
| | PRESSURES YOU WILL NEED TO SUBMIT, GO TO THE WEBSITE: |
| | FLORIDABUILDING.ORG, 2017 FLORIDA BUILDING CODE/ 6TH |
| | EDITION/ TO THE RESIDENTIAL CODE BOOK THEN YOU WILL |
| | NEED TO FIND 2 TABLES TO BE ABLE TO CALCULATE THE |
| | PRESSURES: |
| | TABLE R301.2(2) |
| | TABLE R301.2(3) |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |