2020-08-11 15:10:452ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20071207
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ON THE GAS RISER DIAGRAM IN THIS SUBMITTAL IT
 INDICATES THE PIPE LEAVING THE GAS METER SERVICING THE
 ENTIRE SYSTEM IS A ?? PIPE. YOU ALSO INDICATE THAT THE
 PRESSURE OF THIS SYSTEM IS 12? WC. YOU USED TABLE
 402.4(21) TO SIZE THE PE PIPE TO THE GENERATOR. WITH
 THE INFORMATION THAT YOU HAVE PROVIDED, THE PIPE
 LEAVING THE GAS METER TO SUPPLY THE ENTIRE SYSTEM IS A
 ?? GALVANIZED PIPE FEEDING A LOW PRESSURE SYSTEM. WITH
 THE ADDITION OF 327,000 BTU TO THE ORIGINAL LOW
 PRESSURE SYSTEM WITH A LONGEST LENGTH NOW BECOMING 28?
 THIS ORIGINAL ?? GALVANIZED PIPE CAN ONLY HOLD A VOLUME
 OF 199,000 BTU AND IS UNDERSIZED. FBC FG TABLE
 402.4(2).
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  