| 2020-08-11 15:10:45 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20071207 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ON THE GAS RISER DIAGRAM IN THIS SUBMITTAL IT |
| | INDICATES THE PIPE LEAVING THE GAS METER SERVICING THE |
| | ENTIRE SYSTEM IS A ?? PIPE. YOU ALSO INDICATE THAT THE |
| | PRESSURE OF THIS SYSTEM IS 12? WC. YOU USED TABLE |
| | 402.4(21) TO SIZE THE PE PIPE TO THE GENERATOR. WITH |
| | THE INFORMATION THAT YOU HAVE PROVIDED, THE PIPE |
| | LEAVING THE GAS METER TO SUPPLY THE ENTIRE SYSTEM IS A |
| | ?? GALVANIZED PIPE FEEDING A LOW PRESSURE SYSTEM. WITH |
| | THE ADDITION OF 327,000 BTU TO THE ORIGINAL LOW |
| | PRESSURE SYSTEM WITH A LONGEST LENGTH NOW BECOMING 28? |
| | THIS ORIGINAL ?? GALVANIZED PIPE CAN ONLY HOLD A VOLUME |
| | OF 199,000 BTU AND IS UNDERSIZED. FBC FG TABLE |
| | 402.4(2). |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |