Plan Review Notes
Plan Review Notes For Permit 20071207
Permit Number 20071207
Review Stop G
Sequence Number 1
Notes
Date Text
2020-07-30 10:16:5407/30/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (GENERATOR) TO VERIFY COMPLIANCE WITH 2017 FBC FG
 SEC.305.1 OR 2017 FBC RES. SEC. G2408.1.
  
 4. THE CITY RECORD HAS RECORDS OF AN EXISTING GAS METER
 ON A SYSTEM. THE BTU LOAD OF THE EXISTING GAS SYSTEM
 MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING THE BTU
 LOAD OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE
 TO EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST
 LENGTH OF PIPING FROM THE POINT OF DELIVERY TO THE MOST
 REMOTE OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 5. REGULATOR REQUIRED, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 6. PLEASE SHOW UNION IN FRONT OF REGULATOR 1' OF EITHER
 SIDE AND LABEL ON ISOMETRIC PER THE 2017 FBC RES. SEC
 G2421.2.
  
 7. SHOW DRIP LEG AND LABEL ON ISOMETRIC PER THE 2017
 FBC RES. SEC. G2419.2.
  
 8. SHEETS FOR LOCATION OF GENERATOR AND SURVEY FOR GAS
 LAYOUT ARE ILLEGIBLE. SUBMIT COPIES THAT ARE SCANNED TO
 A PDF FILE, PLASE HAVE CLEAR AND LEGIBLE PLANS FOR
 REVIEW PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  