| 2020-08-11 17:47:22 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT-20071201 |
| | 8/11/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1- WHERE MANHOLE, CLEANOUTS, AND / OR SAMPLE PORT |
| | COVERS ARE LOCATED IN A AREA SUBJECT TO VEHICULAR |
| | TRAFFIC, THE COVERING PLATE, ACCESS DOOR OR CLEAN-OUT |
| | SHALL BE OF AN APPROVED TYPE DESIGNED AND INSTALLED FOR |
| | THIS PURPOSE. |
| | |
| | 2-INTERCEPTORS SHALL BE DESIGNED AND SIZED BY THE |
| | GREASE INTERCEPTOR MANUFACTURE. FACTORY SIZING |
| | CALCULATIONS REQUIRED FROM THE MANUFACTURE FBC 2017 P |
| | 1003.2 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |