| Plan Review Notes For Permit 20071196 |
| Permit Number |
20071196 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-15 12:19:29 | PLAN REVIEW GENERATOR - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | GENERATOR PAD AND DESIGN WIND LOAD CALC'S | | | | | | 1. THE SITE SPECIFIC DESIGN WIND LOAD CALC'S PROVIDED | | | FOR REVIEW ARE BASED ON VULT OF 185MPH AND VASD OF | | | 144MPH WITH A RISK CATEGORY OF III AND AN EXPOSURE | | | CATEGORY OF D. BASED ON THE TABLE PROVIDED THIS | | | ESTABLISHES THE DESIGN WIND LOADS TO BE 53.19PSF FOR | | | PALM BEACH COUNTY. | | | 2. THE ALLOWABLE DESIGN PRESSURE OF THE GENERATOR PAD | | | SUBMITTED IS ONLY 47.44PSF. THIS PAD IS NOT ALLOWED FOR | | | DESIGN WIND LOADS OF 53.19PSF. | | | 3. PLEASE SUBMIT SITE SPECIFIC DESIGN WIND LOAD CALC'S | | | BASED ON PALM BEACH COUNTY'S DESIGN PARAMETERS OF VULT | | | OF 170MPH, (FIGURE R301.2(4) ) VASD OF 132MPH (TABLE | | | R301.2.1.3) RISK CATEGORY I AND EXPOSURE CATEGORY C OR | | | PROVIDE A CONCRETE PAD THAT MEETS OR EXCEEDS THE DESIGN | | | WIND LOADS PROVIDED. | | | | | | | | | | | | | | | |
|