 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 GENERATOR PAD AND DESIGN WIND LOAD CALC'S
  
 1. THE SITE SPECIFIC DESIGN WIND LOAD CALC'S PROVIDED
 FOR REVIEW ARE BASED ON VULT OF 185MPH AND VASD OF
 144MPH WITH A RISK CATEGORY OF III AND AN EXPOSURE
 CATEGORY OF D. BASED ON THE TABLE PROVIDED THIS
 ESTABLISHES THE DESIGN WIND LOADS TO BE 53.19PSF FOR
 PALM BEACH COUNTY.
 2. THE ALLOWABLE DESIGN PRESSURE OF THE GENERATOR PAD
 SUBMITTED IS ONLY 47.44PSF. THIS PAD IS NOT ALLOWED FOR
 DESIGN WIND LOADS OF 53.19PSF.
 3. PLEASE SUBMIT SITE SPECIFIC DESIGN WIND LOAD CALC'S
 BASED ON PALM BEACH COUNTY'S DESIGN PARAMETERS OF VULT
 OF 170MPH, (FIGURE R301.2(4) ) VASD OF 132MPH (TABLE
 R301.2.1.3) RISK CATEGORY I AND EXPOSURE CATEGORY C OR
 PROVIDE A CONCRETE PAD THAT MEETS OR EXCEEDS THE DESIGN
 WIND LOADS PROVIDED.
  
  
  
  
  