| Plan Review Notes For Permit 20071186 |
| Permit Number |
20071186 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-22 11:37:14 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC B 107.2.1. FBC B 1207.2 & 1207.3. SUBMITTED TEST | | | REPORTS (STC) AND (IIC) FOR ECLIPSE II ACOUSTICAL | | | UNDERLAYMENT FOR FLOATING/LAMINATE/ENGINEERED WOOD | | | FLOORS/WPC (SOLID CORE VINYL PLANKS) WITH MOISTURE | | | BARRIER CONTAIN DROP CEILINGS IN THE TEST ASSEMBLY. | | | TEST REPORTS CANNOT INCLUDE DROPPED GYPSUM CEILINGS. | | | PLEASE PROVIDE TWO SETS OF TEST REPORTS WITHOUT DROPPED | | | GYPSUM CEILINGS. | | | |
|