| Plan Review Notes For Permit 20071177 |
| Permit Number |
20071177 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-05 17:43:06 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) HI LIGHT OR CIRCLE ALL OF THE APPROPIATE ITEMS IN | | | THE PRODUCT APPROVAL INCLUDING THE DESIGN PRESSURE AND | | | TYPE OF INSULATION. FBC 107.2 | | | | | | 2) THE ROOFING SYSTEM THAT WAS SUBMITTED TYPE A(4) ON | | | PAGES15-16 OF THE PRODUCT APPROVAL REQUIRES AT LEAST | | | ONE LAYER OF THE LISTED INSULATIONS. THE MAXIMUM DESIGN | | | PRESSURE FOR THIS SYSTEM IS -60 PSF, WHICH IS TOO LOW | | | FOR THE PERIMETER AND CORNER ROOF AREAS. THE LIMITATION | | | #7 REQUIRES THAT SIGNED AND SEALED CALCULATIONS ARE | | | SUBMITTED FOR ENHANCED FASTENING IN THESE AREAS TO | | | INCREASE THE DESIGN PRESSURES. SUBMIT THE REQUIRED | | | DOCUMENTS. FBC 107.2 | | | | | | 3) SUBMIT A ROOF DIAGRAM OF THE BUILDING. SPECIFY THE | | | ROOF HEIGHT AND SHOW DIMENSIONS OF THE ROOF. INDICATE | | | ANY ROOF DRAINS, PARAPET WALLS, SCUPPERS, ETC. FBC | | | 107.2.1 |
|