| 2020-08-06 16:31:46 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- PLUMBING PLAN REVIEW |
| | W. P. B. PERMIT PRIME: 20071161 |
| | W. P. B. PLUMBING PERMIT: 20071163 |
| | ADD: 550 OKEECHOBEE BLVD. |
| | PLUMB.CONT: SBL CONSTRUCTION GROUP |
| | TEL: 561-676-6060 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. AUGUST 06/2020 |
| | ACTION: DENIED |
| | |
| | 1) THERE WERE NO PLANS SUBMITTED FOR PLUMBING. THE |
| | PLUMBING CONTRACTOR MUST DRAW THEIR OWN PLANS FOR THE |
| | SHOWER PAN. |
| | CERTIFICATION BY CONTRACTOR. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE. 107.3.4.3 |
| | CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION |
| | TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/ |
| | PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES |
| | THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN |
| | THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS |
| | THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| | TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| | THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| | NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| | DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| | AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| | SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | 2) PLEASE PROVIDE DETAILS FOR THE SHOWER PAN COMPLYING |
| | WITH SECTION 417.5.2 OF THE 2017 FBC-P. |
| | |
| | 3) THE SCOPE OF WORK INDICATES THE SHOWER VALVE IS TO |
| | BE REPLACED BUT DOES NOT PROVIDE THE SPEC SHEET ON THE |
| | SHOWER VALVE AND COMPLIANCE WITH SECTION 424.3 |
| | INDIVIDUAL SHOWER VALVES 2017 FBC-P. SHOWER VALVES |
| | SHALL BE REQUIRED WITH A MEANS TO LIMIT THE MAXIMUM |
| | SETTING OF THE VALVE TO 120 DEGREES FAHRENHEIT. |
| | |
| | 4) PLEASE SHOW ON THE FLOOR PLAN WHICH WALL WILL HAVE |
| | THE SHOWER VALVE AND SHOWER HEAD. AGAIN THE CONCERN IS |
| | IF THEY ARE IN THE FIRE RATED WALL PROTECTION AROUND |
| | THE OPENING IN THE 1 HOUR FIRE PARTITION. SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B 708.7 PENETRATIONS. |
| | PENETRATIONS OF FIRE RATED WALLS SHALL COMPLY WITH |
| | SECTION 714. |
| | SEE 714.3.2 MEMBRANE PENETRATIONS. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |