Text |
| 2020-08-31 11:14:05 | FAILED |
| | |
| | FASCIA IDENTITY SIGN |
| | |
| | 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA STOREFRONT |
| | TYPE 1 ONLY ALLOWS A FASCIA IDENTITY SIGN ON A CASE BY |
| | CASE BASIS IF IT HAS BEEN GRANTED WRITTEN APPROVAL BY |
| | CITYPLACE RETAIL AS A WAIVER I. PLEASE PROVIDE THE |
| | WAIVER I APPROVAL LETTER FROM CITYPLACE RETAIL WHICH |
| | SPECIFICALLY GRANTS THE APPROVAL FOR THE FASCIA |
| | IDENTITY SIGN. |
| | |
| | 2) THE HORIZONTAL DIMENSION OF THE FASCIA IS LISTED AS |
| | 59.9 INCHES (") WHEN IT SHOULD BE SHOWN AS 59.9 FEET. |
| | |
| | 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE |
| | THAT FASCIA IDENTITY SIGNS BE CENTERED BOTH VERTICALLY |
| | AND HORIZONTALLY WITHIN THE FASCIA SIGN BAND AREA. |
| | PLEASE PROVIDE THE DIMENSIONS ON THE PLAN SO STAFF CAN |
| | VERIFY COMPLIANCE WITH THIS REQUIREMENT. |
| | |
| | 4) THE CURRENT ROSEMARY SQUARE TENANT SIGN CRITERIA |
| | REQUIRES A MINIMUM OF 6 INCHES BETWEEN THE COPY AREA |
| | AND THE EDGE OF THE FASCIA; HOWEVER, THERE IS A CURRENT |
| | AMENDMENT UNDER REVIEW BY THE CITY WHICH WOULD REDUCE |
| | THE BOARDER TO 3 INCHES IF APPROVED ON SEPTEMBER 8, |
| | 2020. NOTE: IT APPEARS FROM THE DRAWING THAT BOTH |
| | STANDARDS ARE MET, BUT STAFF REQUIRES THE DIMENSIONS TO |
| | VERIFY. |
| | |
| | 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE |
| | THAT FASCIA IDENTITY SIGNS ARE MOUNTED AT NO POINT |
| | HIGHER THAN 16 FEET FROM THE FINISHED FLOOR. PLEASE |
| | PROVIDE THE DIMENSION FOR STAFF TO VERIFY. |
| | |
| | 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE |
| | THAT THE INDIVIDUAL LETTERS FOR FASCIA IDENTITY SIGNS |
| | SHALL BE AT LEAST 1/2 INCH THICK. THE PROPOSED SIGN IS |
| | SHOWN AS ONLY 1/4 INCH THICK AND THUS DOES NOT COMPLY |
| | WITH THE MINIMUM REQUIREMENTS. |
| | |
| | 7) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE |
| | THAT THE ANCHOR BOLTS BE 316 STAINLESS STEEL. REMOVE |
| | THE 6061-T6 ALUM OPTION FROM THE ANCHOR NOTES SECTION |
| | OF THE PLANS. |
| | |
| | 8) THE SIGN ELEVATION DRAWING INCLUDES A NOTE STATING |
| | "APPROX ANCHOR LOCATIONS (TYP)" WHICH IS MISLEADING |
| | WHEN COMPARED TO THE PERSPECTIVE VIEW DRAWING. THE |
| | SAMPLE LETTER "T" SHOWS FOUR ANCHORS ON THE PERSPECTIVE |
| | DRAWING AND ONLY THREE ON THE ELEVATION DRAWING. |
| | ADDITIONALLY, THE ELEVATION DRAWING SHOWS THEM FOR WHAT |
| | APPEARS TO BE A SOLID LETTER WHILE THE PERSPECTIVE VIEW |
| | SHOWS THEM BEHIND THE FRAME OF THE LETTER OUTLINE. |
| | PLEASE ENSURE ALL DRAWINGS SHOW SAME CONDITIONS OR |
| | INCLUDE NOTES WHICH CLEARLY INDICATED WHAT IS BEING |
| | DEPICTED. |
| | |
| | 9) THE ANCHOR NOTES STATE THAT THE LETTERS WILL BE |
| | DRILLED TO RECEIVE THE STUDS. PROVIDE DETAILS ON HOW |
| | THE BOLT ENDS CONFORM TO THE ROSEMARY SQUARE TENANT |
| | SIGN CRITERIA REQUIREMENT THAT RIVETS, SCREWS AND OTHER |
| | FASTENERS SHALL BE FLUSH, FILLED OR FINISHED TO BE |
| | UNNOTICEABLE. |
| | |
| | 10) THE LIGHTING REQUIRES A SEPARATE PERMIT, WITH |
| | PLANS. |
| | |
| | |
| | PERMITTED: 59.9 SF |
| | PROPOSED: 24.43 SF |