Plan Review Notes
Plan Review Notes For Permit 20071139
Permit Number 20071139
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-09-17 10:45:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE ACCESS GATES DO NOT APPEAR TO MEET PREVIOUS SITE
 APPROVAL FOR FD ACCESS REQUIREMENTS.
  
 15' ON THE FRONT NORTH AND 13' ON THE SOUTH IS TOO
 NARROW. THE REAR GATE IS APPROVED AS IS AS IT WAS
 PREVIOUSLY ACCEPTED DUE TO LIMITED PROPERTY LINES.
  
 20' IS REQUIRED WITH 18' BEING ACCEPTABLE AND LESSER
 DIMENSIONS ON A CASE BY CASE BASIS.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE AS WIDE A WIDTH
 AS POSSIBLE.
  
  
 2) ADD A KNOX KEY SWITCH ON THE REAR GATE FOR AN
 ALTERNATIVE FS ACCESS POINT.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  