| 2020-09-01 11:23:27 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| | HEADING ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT |
| | APPROVAL?; PROVIDE INFORMATION FROM SHEETS 6 & 7 OF |
| | FL1850 USE ALPHABETICAL LETTER THAT CORRESPONDS WITH |
| | THE CONNECTION TYPE FOR THE TOP AND BOTTOM CONNECTIONS. |
| | PLEASE CORRECT COLUMN HEADING ?ANCHOR SPACING? PLEASE |
| | NOTE PAGE 13 OF 20, FACTORS APPLY USING ANCHOR ALL |
| | POINT SOLID SET WITH A 3? MIN. EDGE DISTANCE REQUIRES A |
| | 0.78 FACTOR. REDUCE ANCHOR SPACING BY MULTIPLYING |
| | SPACING SHOWN ON SCHEDULE BY THE FACTOR. |
| | 2. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC |
| | R 310.4; INCLUDE ROOM DESIGNATION. SECOND REQUEST. |
| | |