Plan Review Notes
Plan Review Notes For Permit 20071072
Permit Number 20071072
Review Stop B
Sequence Number 2
Notes
Date Text
2020-09-01 11:23:27JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT
 APPROVAL?; PROVIDE INFORMATION FROM SHEETS 6 & 7 OF
 FL1850 USE ALPHABETICAL LETTER THAT CORRESPONDS WITH
 THE CONNECTION TYPE FOR THE TOP AND BOTTOM CONNECTIONS.
 PLEASE CORRECT COLUMN HEADING ?ANCHOR SPACING? PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY USING ANCHOR ALL
 POINT SOLID SET WITH A 3? MIN. EDGE DISTANCE REQUIRES A
 0.78 FACTOR. REDUCE ANCHOR SPACING BY MULTIPLYING
 SPACING SHOWN ON SCHEDULE BY THE FACTOR.
 2. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION. SECOND REQUEST.
  