| 2020-08-05 10:45:38 | PLAN REVIEW - BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. DESIGN PARAMETERS - FBC EXISTING BUILDING ALTERATION |
| | LEVEL 2 |
| | SECTION 504 |
| | ALTERATION?LEVEL 2 |
| | 504.1SCOPE. |
| | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| | 504.2 APPLICATION. LEVEL 2 ALTERATIONS SHALL COMPLY |
| | WITH THE PROVISIONS OF CHAPTER 7 FOR LEVEL 1 |
| | ALTERATIONS AS WELL AS THE PROVISIONS OF CHAPTER 8. |
| | |
| | 2. PROVIDE EXTERIOR ELEVATION PLAN. INCLUDE FRAMING |
| | DETAILS FASTENER SCHEDULE AND DEMENSIONS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 3. NOTE ON WIND LOAD CALCULATIONS STATES RESULTS ARE |
| | NOT VALID WITHOUT AN ORIGINAL SIGNATURE AND RAISED SEAL |
| | BY A LICENSED PROFESSIONAL ENGINEER. |
| | SUBMIT WINDLOAD CALC'S WITH VALID DIGITAL SIGNATURE OF |
| | DESIGN PROFESSIONAL. |
| | OPTION - YOU MAY REMOVE THIS NOTE AND HAVE THE |
| | CONTRACTOR SIGN THE WIND LOAD CALC'S. |
| | |
| | 4. PRODUCT APPROVAL FL21855-R1. DESIGNER TO SELECT |
| | MODEL OF DOOR TO BE INSTALLED. IF NON-IMPACT RATED DOOR |
| | IS SELECTED PROVIDE OPENING PROTECTION DEVICE. |
| | DESIGNER/CONTRACTOR TO REVIEW AND APPROVE PRODUCT |
| | APPROVALS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 5. LANDING REQUIRED AT EXTERIOR DOORS. |
| | R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE |
| | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| | MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| | DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE |
| | PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT |
| | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |