Plan Review Notes
Plan Review Notes For Permit 20071065
Permit Number 20071065
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-18 12:09:411) SUBNMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATERPROOFING SYSTEM
 TO BE INSTALLED FOR THE SHOWER. THE SYSTEM SHALL COMPLY
 WITH FBC-PLUMBING SEC.417.5.2.5 OR SEC. 417.5.2.6.
 2) SUBMIT AN APPLICATION FROM A LICENSE PLUMBING
 CONTRACTOR FOR THE INSTALLATION OF THE NEW SHOWER AND
 VALVE AND VANITY. THIS WORK MUST BE DONE BY A LICENSED
 PLUMBING CONTRACTOR. A GENERAL CONTRACTOR IS NOT
 AUTHORIZED TO DO THIS SCOPE OF WORK. FL.STATUTE SEC.
 489.103.
 3) THE SHOWER SHALL BE PITCHED 1/4 INCH PER FOOT
 MINIMUM TOWARD THE DRAIN. FBC-PLUMBING SEC.417.5.2.
 4) SUBMIT SPECIFICATIONS FOR THE SHOWER VALVE. THE
 VALVE SHALL COMPLY WITH FBC-PLUMBING SEC.424.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW