| Notes |
| Date |
Text |
| 2020-08-18 12:09:41 | 1) SUBNMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE WATERPROOFING SYSTEM | | | TO BE INSTALLED FOR THE SHOWER. THE SYSTEM SHALL COMPLY | | | WITH FBC-PLUMBING SEC.417.5.2.5 OR SEC. 417.5.2.6. | | | 2) SUBMIT AN APPLICATION FROM A LICENSE PLUMBING | | | CONTRACTOR FOR THE INSTALLATION OF THE NEW SHOWER AND | | | VALVE AND VANITY. THIS WORK MUST BE DONE BY A LICENSED | | | PLUMBING CONTRACTOR. A GENERAL CONTRACTOR IS NOT | | | AUTHORIZED TO DO THIS SCOPE OF WORK. FL.STATUTE SEC. | | | 489.103. | | | 3) THE SHOWER SHALL BE PITCHED 1/4 INCH PER FOOT | | | MINIMUM TOWARD THE DRAIN. FBC-PLUMBING SEC.417.5.2. | | | 4) SUBMIT SPECIFICATIONS FOR THE SHOWER VALVE. THE | | | VALVE SHALL COMPLY WITH FBC-PLUMBING SEC.424.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|