| 2020-08-17 14:10:08 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20071065 |
| | ADD: 525 S. FLAGLER DR. # 27B |
| | CONT: THE CASTELLA & GODOY COMPANIES |
| | TEL: 561-723-4144 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY AUGUST 17TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE FLOOR PLAN SHEET 101.2 INDICATES IN THE |
| | TITLEBLOCK IT WAS DEVELOPED BY THE CONTRACTOR OF |
| | RECORD, PLEASE FOLLOW THE REQUIREMENTS FOR PLANS |
| | DESIGNED BY CONTRACTORS. |
| | CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY |
| | CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT |
| | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE |
| | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| | TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| | THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| | NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| | DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| | AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| | SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | 2) THE CONTRACTOR HAS NOT INDICATED WHICH METHOD UNDER |
| | THE 2017 EXISTING BUILDING CODE THE PLANS WERE |
| | DESIGNED. IF UNDER THE WORK AREA METHOD THIS WOULD BE |
| | CONSIDERED A LEVEL I. |
| | 2017 EXISTING BUILDING CODE METHOD OF PLAN DEVELOPMENT. |
| | 2017 EXISTING BUILD. CODE SECTION 301.1. THE REPAIRS, |
| | ALTERATIONS, CHANGE OF OCCUPANCY, ADDITIONS OR |
| | RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH |
| | ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH |
| | 301.1.3 AS SELECTED BY THE DESIGNER OF RECORD. |
| | 3) SHEET 101.2 NEITHER THE NOTES NOR DETAIL INDICATE IF |
| | THE ? INCH DENSE-SHIELD AND TILE ARE GOING TO BE |
| | INSTALLED? SEE THE 2017 FBC-B SHOWERS & TUBS 1210.3. |
| | SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER |
| | HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO |
| | A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | 4) |
| | |
| | |
| | |