| Date |
Text |
| 2020-09-15 11:14:28 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| | [email protected] |
| | |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | ` |
| | 1. FBC B 107.2.1 ON THE SCHEDULE FOR INSTALLATION OF |
| | PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| | HEADING ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT |
| | APPROVAL?. WALL CONNECTION TYPES (A), (B), (C), (D), |
| | (E) OR (F) CANNOT BE USED FOR SHUTTER SPANS THAT |
| | EXCEEDS 13?-1? FOR A.S.D. DESIGN PRESSURE RATING + OR ? |
| | 45 P.S.F. CONNECTION TYPES ALLOWED FOR SPANS OF 168? |
| | ARE CONNECTION TYPE (G) (CEILING MOUNTING); (H),(I) AND |
| | (I1) (FLOOR MOUNTING) USING POURED CONCRETE SUBSTRATE. |
| | PROVIDE THE CORRECT MOUNTING CONNECTION AND ANCHOR |
| | SPACINGS AS PER THE CONNECTION TYPES USED. PLEASE |
| | CORRECT FOR ITEMS #1-4 ON THE SCHEDULE FOR INSTALLATION |
| | OF OPENING PROTECTIVE DEVICES OR ASSEMBLIES. SECOND |
| | REQUEST |
| | |