| Plan Review Notes For Permit 20071059 |
| Permit Number |
20071059 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-13 14:31:16 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | | | | 1. FBC B 107.2.1 FOR WALL CONNECTION TYPE C/F REFER TO | | | FL389.2 SHEET 11, SCHEDULE #1 OR SCHEDULE #2; MAXIMUM | | | A.S.D. DESIGN PRESSURE RATING 45 THE MAXIMUM SHUTTER | | | SPAN IS 13?-1?/157?. SHUTTER SPAN OF 168? EXCEEDS | | | MAXIMUM SPAN ALLOWED FOR WALL MOUNTED CONNECTIONS. | | | PLEASE CORRECT FOR ITEMS #1-4 ON THE SCHEDULE FOR | | | INSTALLATION OF OPENING PROTECTIVE DEVICES OR | | | ASSEMBLIES. | | | |
|