| Plan Review Notes For Permit 20071059 |
| Permit Number |
20071059 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-31 09:17:37 | SHUTTERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ATTACHMENT SPACING FOR THE 168" SHUTTERS USING | | | CONNECTION TYPE "D" AND (-43.6 ) PRESSURE ARE NOT | | | CORRECT ON THE "OPENING INSTALLATION SCHEDULE" (ALSO | | | CHECK THE SHUTTER SPAN CHART FOR THE (168") SHUTTER) | | | |
|