| Plan Review Notes For Permit 20071019 |
| Permit Number |
20071019 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-05 08:49:25 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - | | | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | | ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON | | | THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL | | | SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A | | | HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT | | | APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE | | | PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND | | | DESIGN DATA USED ON THE ADDITIONAL ATTACHMENT DETAILS | | | PER 2017 FBC AND ASCE 7-10 - WIND SPEED - EXPOSURE - | | | RISK CATEGORY - ETC. | | | 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE SHINGLES. | | | |
|