Plan Review Notes
Plan Review Notes For Permit 20071019
Permit Number 20071019
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-05 08:49:25ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND
 DESIGN DATA USED ON THE ADDITIONAL ATTACHMENT DETAILS
 PER 2017 FBC AND ASCE 7-10 - WIND SPEED - EXPOSURE -
 RISK CATEGORY - ETC.
 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE SHINGLES.
  