| Plan Review Notes For Permit 20070965 |
| Permit Number |
20070965 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-09-17 16:06:11 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS FOR THE BERTHA ACCORDION | | | SHUTTERS ARE ILLEGIBLE. I CAN NOT SEE THE ANCHOR | | | SPACING TABLES THEY ARE NOT LEGIBLE. UPLOAD CLEAR | | | COPIES OF THE PRODUCT APPROVAL. FBC 107.2.1 | | | | | | 2) THE WINDLOAD CALCULATIONS THAT WERE UPLOADED ARE | | | COPIES FROM AND ENGINEER. WHEN YOU SUBMIT DOCUMENTS | | | FROM AN ENGINEER THEY ARE REQUIRED TO HAVE THE | | | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IF PAPER AND | | | HIS DIGITAL SIGNATURE IF ELECTRONICALLY SUBMITTED. FS | | | 471 AND FAC 61G-15 |
|