| 2020-08-26 13:26:55 | ROOFED PATIO |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | |
| | 2ND REVIEW |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE SHOW THE ROOF SLOPE (MIN. 1/4 IN 12) ON THE |
| | DRAWINGS TO COMPLY WITH FBC R905.9.1 |
| | 2) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - |
| | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE |
| | ROOFING PRODUCT APPROVAL - SEE PAGE 21 OF 27 IN THE |
| | PRODUCT APPROVAL WHERE DECK TYPE "WOOD NON-INSULATED" |
| | STARTS THEN CIRCLE A ROOFING "SYSTEM TYPE" AND |
| | "ATTACHMENT OPTION" ETC. THERE ARE MORE OPTIONS ON THE |
| | PRECEDING PAGES OF THE PRODUCT APPROVAL - ROOFING |
| | SYSTEM TO BE USED ON THE PROVIDED PRODUCT APPROVAL MAY |
| | REQUIRE ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS |
| | FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND |
| | 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM |
| | SHOWN ON THE PRODUCT APPROVAL - SEE GENERAL LIMITATION |
| | NOTE NUMBER 7 ON THE PRODUCT APPROVAL. OR PROVIDE A |
| | STATEMENT THAT YOU WOULD LIKE TO DEFER THE ROOFING |
| | SUBMITTALS. |
| | |
| | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY |
| | SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE |
| | BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |