Plan Review Notes
Plan Review Notes For Permit 20070953
Permit Number 20070953
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-14 11:10:51ROOFED PATIO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ROOF SLOPE (MIN. 1/4 IN 12) ON THE
 DRAWINGS TO COMPLY WITH FBC R905.9.1
 2) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE
 PRODUCT APPROVAL.
  