2020-09-12 10:31:16PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. NEW ROOM COMMUNICATES FREELY WITH EXISTING
 RESIDENCE. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC
 EC.
  
 PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM
 SIZING CALCULATIONS- SECTION R403.7.1 FBC EC.
  
 2. DEMONSTRATE COMPLIANCE WIT FBC R 303.10 REQUIRED
 HEATING
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING.
  
 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS,
 SECTION 1101.1 SCOPE. AN ADDITION TO A BUILDING OR
 STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AS ADOPTED FOR NEW CONSTRUCTION.
 SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, ENERGY.
  
 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS,
 SECTION R502 ADDITIONS,
  
 ADDITIONS
 R502.1 GENERAL.
 ADDITIONS TO AN EXISTING BUILDING, BUILDING SYSTEM OR
 PORTION THEREOF SHALL CONFORM TO THE PROVISIONS OF THIS
 CODE AS THOSE PROVISIONS RELATE TO NEW CONSTRUCTION
 WITHOUT REQUIRING THE UNALTERED PORTION OF THE EXISTING
 BUILDING OR BUILDING SYSTEM TO COMPLY WITH THIS CODE.
 ADDITIONS SHALL NOT CREATE AN UNSAFE OR HAZARDOUS
 CONDITION OR OVERLOAD EXISTING BUILDING SYSTEMS. AN
 ADDITION SHALL BE DEEMED TO COMPLY WITH THIS CODE WHERE
 THE ADDITION ALONE COMPLIES, WHERE THE EXISTING
 BUILDING AND ADDITION COMPLY WITH THIS CODE AS A SINGLE
 BUILDING, OR WHERE THE BUILDING WITH THE ADDITION USES
 NO MORE ENERGY THAN THE EXISTING BUILDING. ADDITIONS
 SHALL BE IN ACCORDANCE WITH SECTION R502.1.1, R502.1.2
 OR R502.1.3.
  
  
  
  
  
  