| Plan Review Notes For Permit 20070907 |
| Permit Number |
20070907 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-21 16:23:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, IT APPEARS THAT A PREFAB SLAB IS | | | PROPOSED. EITHER: | | | | | | PROVIDE ENGINEERING FOR THE PREFAB SLAB, OR | | | | | | PROVIDE A STRUCTURAL DETAIL WITH ALL INFORMATION | | | INCLUDING CALCULATIONS TO SHOW HOW THE PROPOSED PREFAB | | | SLAB WILL RESIST WIND LOADS, INCLUDING OVERTURNING AND | | | SLIDING. THE DETAIL PROVIDED LACKS BASIC INFORMATION | | | SUCH AS THICKNESS, DETAIL FOR THE SLAB CONSTRUCTION, | | | REINFORCING STEEL, WIND DESIGN CRITERIA, ETC. | | | | | | |
|