| Plan Review Notes For Permit 20070903 |
| Permit Number |
20070903 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-07-24 16:53:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) OUTLETS WITHIN 6' OF SINKS SHALL BE GFCI PROTECTED | | | PER 210.8(B) | | | | | | 2) AIC RATING REQUIRED FOR SERVICE AND LABELS 110.9, | | | 110,10, 110.24 |
|