Plan Review Notes
Plan Review Notes For Permit 20070892
Permit Number 20070892
Review Stop E
Sequence Number 1
Notes
Date Text
2020-08-12 19:38:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO SMOKE ALARMS SHOWN. PROVIDE CORRECTION FBC-R 314
 &315
  
 2. ELECTRICAL RISER SHOWS 3-2/0 AND 1-#6 GROUND FROM
 METER CAN TO SERVICE DISCONNECTING MEANS. THIS PROVIDES
 A PARALLEL PATH BACK TO THE GROUNDED CONDUCTOR WHICH IS
 NOT PERMITTED. REMOVE EQUIPMENT GROUNDING CONDUCTOR
 FROM RISER. NEC 250.24B ALSO REMOVE GROUND FROM PIPE
 FROM TRANSFORMER TO METER.
  
 3. GROUNDING ELECTRODE SYSTEM SHOWS #6 GEC TO GROUND
 RODS, C/W PIPE, AND BUILDING STEEL. #6 IS INSUFFICIENT
 SIZE TO CONNECT TO C/W PIPE AND BUILDING STEEL. PROVIDE
 CORRECTION. NEC 250.66A&B
  
 4. NO INTERSYSTEM CONNECTION (BONDING BRIDGE) SHOWN ON
 RISER DIAGRAM NEC 250.94
  
 5. LOAD CALCULATION IS INCORRECT. CHECK MATH. FIRST 10K
 AT 100% THEN THE REMAINDER OF THE GENERAL LOAD AT 40%
 WOULD BE 18,776W NOT 14,776W.
  
 HEATER IS SPELLED HEATHER.
  
 PROVIDE ACCURATE LOAD CALCULATION SHOWING PREVIOUS LOAD
 AND ADDITION OF NEW LOADS. NEC 220
  
 6. PERMIT APPLICATION FOR ELECTRICAL HAS NO CONTRACTOR
 NAMED OR AN OWNER BUILDER DESIGNATION AND HAS NO VALUE
 ASSIGNED TO IT. PLEASE COMPLETE PERMIT APP. IF VALUE IS
 INCLUDED IN MASTER PERMIT FOR ELECTRIC ANNOTATE THAT ON
 PERMIT APP.. FBC 107.2.1
  
 7. RELOCATED METER AND NEW PANEL PLACEMENT SHOWN ON
 PLAN BUT NO LOCATION OF SERVICE DISCONNECT IS PROVIDED.
 SHOW LOCATION ON PLAN. FBC 107.2.1
  
 8. PROVIDE ARC-FAULT PROTECTION WHERE NEEDED PER NEC
 210.12.
  
 9. PROVIDE NOTE ON PLAN THAT RECEPTACLES WILL BE TAMPER
 PROOF PER NEC 406.12
  
 10. SHOW LOCATION AND DISCONNECT FOR MINI-SPLIT
 COMPRESSOR UNIT. FBC 107.2.1
  
 11. RELOCATED WASHER RECEPTACLE MUST BE AFCI/GFCI
 PROTECTED PER NEC 210.12B AND NEC 210.8
  
 12. RECEPTACLE REQUIRED TO RIGHT OF ENTRY DOOR PER NEC
 210.52
  
 13. WASHER/DRYER CIRCUIT SHOWN AT #10 WIRE WITH 40AMP
 OVERCURRENT PROTECTION. THIS IS A VIOLATION PER NEC
 240.4. PROVIDE CORRECTION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved