| 2020-08-12 19:38:32 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO SMOKE ALARMS SHOWN. PROVIDE CORRECTION FBC-R 314 |
| | &315 |
| | |
| | 2. ELECTRICAL RISER SHOWS 3-2/0 AND 1-#6 GROUND FROM |
| | METER CAN TO SERVICE DISCONNECTING MEANS. THIS PROVIDES |
| | A PARALLEL PATH BACK TO THE GROUNDED CONDUCTOR WHICH IS |
| | NOT PERMITTED. REMOVE EQUIPMENT GROUNDING CONDUCTOR |
| | FROM RISER. NEC 250.24B ALSO REMOVE GROUND FROM PIPE |
| | FROM TRANSFORMER TO METER. |
| | |
| | 3. GROUNDING ELECTRODE SYSTEM SHOWS #6 GEC TO GROUND |
| | RODS, C/W PIPE, AND BUILDING STEEL. #6 IS INSUFFICIENT |
| | SIZE TO CONNECT TO C/W PIPE AND BUILDING STEEL. PROVIDE |
| | CORRECTION. NEC 250.66A&B |
| | |
| | 4. NO INTERSYSTEM CONNECTION (BONDING BRIDGE) SHOWN ON |
| | RISER DIAGRAM NEC 250.94 |
| | |
| | 5. LOAD CALCULATION IS INCORRECT. CHECK MATH. FIRST 10K |
| | AT 100% THEN THE REMAINDER OF THE GENERAL LOAD AT 40% |
| | WOULD BE 18,776W NOT 14,776W. |
| | |
| | HEATER IS SPELLED HEATHER. |
| | |
| | PROVIDE ACCURATE LOAD CALCULATION SHOWING PREVIOUS LOAD |
| | AND ADDITION OF NEW LOADS. NEC 220 |
| | |
| | 6. PERMIT APPLICATION FOR ELECTRICAL HAS NO CONTRACTOR |
| | NAMED OR AN OWNER BUILDER DESIGNATION AND HAS NO VALUE |
| | ASSIGNED TO IT. PLEASE COMPLETE PERMIT APP. IF VALUE IS |
| | INCLUDED IN MASTER PERMIT FOR ELECTRIC ANNOTATE THAT ON |
| | PERMIT APP.. FBC 107.2.1 |
| | |
| | 7. RELOCATED METER AND NEW PANEL PLACEMENT SHOWN ON |
| | PLAN BUT NO LOCATION OF SERVICE DISCONNECT IS PROVIDED. |
| | SHOW LOCATION ON PLAN. FBC 107.2.1 |
| | |
| | 8. PROVIDE ARC-FAULT PROTECTION WHERE NEEDED PER NEC |
| | 210.12. |
| | |
| | 9. PROVIDE NOTE ON PLAN THAT RECEPTACLES WILL BE TAMPER |
| | PROOF PER NEC 406.12 |
| | |
| | 10. SHOW LOCATION AND DISCONNECT FOR MINI-SPLIT |
| | COMPRESSOR UNIT. FBC 107.2.1 |
| | |
| | 11. RELOCATED WASHER RECEPTACLE MUST BE AFCI/GFCI |
| | PROTECTED PER NEC 210.12B AND NEC 210.8 |
| | |
| | 12. RECEPTACLE REQUIRED TO RIGHT OF ENTRY DOOR PER NEC |
| | 210.52 |
| | |
| | 13. WASHER/DRYER CIRCUIT SHOWN AT #10 WIRE WITH 40AMP |
| | OVERCURRENT PROTECTION. THIS IS A VIOLATION PER NEC |
| | 240.4. PROVIDE CORRECTION. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |