| 2020-08-24 09:27:43 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PLEASE ADDRESS FBC-R314.3.1 ALTERATIONS, REPAIRS AND |
| | ADDITIONS. WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 2) PLEASE ADDRESS IF APPLICABLE FBC-R315.1 CARBON |
| | MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR AN |
| | ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT FOR |
| | NEW CONSTRUCTION IS ISSUED AND HAVING A |
| | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, |
| | AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR |
| | ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF |
| | COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE |
| | ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR |
| | SLEEPING PURPOSES. |
| | |
| | 3) FBC ENERGY CONSERVATION SECTION R101.4.5 REQUIRES |
| | ANY UNCONDITIONED SPACE THAT IS ALTERED TO BECOME |
| | CONDITIONED SPACE TO BE BROUGHT INTO FULL COMPLIANCE |
| | WITH THE ENERGY CODE. SUBMIT TWO SETS OF FORMS AND |
| | DOCUMENTS TO SHOW COMPLIANCE. FBC ENERGY CONSERVATION |
| | SECTION R103. |
| | |
| | 4) SPECIFY THE REQUIRED WALL INSULATION ON THE PLANS. |
| | FBC ENERGY CONSERVATION AND CITY AMENDMENTS FBC 107.2.1 |
| | |
| | 5) SHOW THAT ADEQUATE ATTIC VENTILATION IS PROVIDED AS |
| | REQUIRED BY R806.1 & R806.2. ENCLOSED ATTICS AND |
| | ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE |
| | APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL |
| | HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY |
| | VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF |
| | RAIN OR SNOW. VENTILATION OPENINGS SHALL HAVE A LEAST |
| | DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH |
| | (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A LEAST |
| | DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING, |
| | HARDWARE CLOTH OR SIMILAR MATERIAL WITH OPENINGS HAVING |
| | A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 |
| | INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS |
| | SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.7. |
| | REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO |
| | THE OUTSIDE AIR. |
| | |
| | 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE |
| | DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE |
| | SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT |
| | BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED |
| | TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 7) THE NEW FLOOR PLAN ON SHEET A2 SHOWS A PREFAB SHED |
| | FOR THE LAUNDRY EQUIPMENT AND IT IS NOT SHOWN ON THE |
| | SITE PLAN. IS THIS SHED GOING TO BE APPLIED FOR UNDER A |
| | SEPARATE PERMIT? IF IT WILL BE UNDER THIS PERMIT, ADD |
| | IT TO THE SITE PLAN AND SUBMIT THE SITE SPECIFIC |
| | ENGINEERING OR MANUFACTURED BUILDING DOCUMENTS FOR THE |
| | SHED. CITY AMENDMENTS FBC 107.2.1 & FBC 107.3.5.3 |
| | |
| | 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |