Plan Review Notes
Plan Review Notes For Permit 20070892
Permit Number 20070892
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-24 09:27:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLEASE ADDRESS FBC-R314.3.1 ALTERATIONS, REPAIRS AND
 ADDITIONS. WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2) PLEASE ADDRESS IF APPLICABLE FBC-R315.1 CARBON
 MONOXIDE PROTECTION. EVERY SEPARATE BUILDING OR AN
 ADDITION TO AN EXISTING BUILDING FOR WHICH A PERMIT FOR
 NEW CONSTRUCTION IS ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR
 ELEMENT THAT EMITS CARBON MONOXIDE AS A BYPRODUCT OF
 COMBUSTION SHALL HAVE AN OPERATIONAL CARBON MONOXIDE
 ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES.
  
 3) FBC ENERGY CONSERVATION SECTION R101.4.5 REQUIRES
 ANY UNCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE TO BE BROUGHT INTO FULL COMPLIANCE
 WITH THE ENERGY CODE. SUBMIT TWO SETS OF FORMS AND
 DOCUMENTS TO SHOW COMPLIANCE. FBC ENERGY CONSERVATION
 SECTION R103.
  
 4) SPECIFY THE REQUIRED WALL INSULATION ON THE PLANS.
 FBC ENERGY CONSERVATION AND CITY AMENDMENTS FBC 107.2.1
  
 5) SHOW THAT ADEQUATE ATTIC VENTILATION IS PROVIDED AS
 REQUIRED BY R806.1 & R806.2. ENCLOSED ATTICS AND
 ENCLOSED RAFTER SPACES FORMED WHERE CEILINGS ARE
 APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF RAFTERS SHALL
 HAVE CROSS VENTILATION FOR EACH SEPARATE SPACE BY
 VENTILATING OPENINGS PROTECTED AGAINST THE ENTRANCE OF
 RAIN OR SNOW. VENTILATION OPENINGS SHALL HAVE A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A LEAST
 DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH OR SIMILAR MATERIAL WITH OPENINGS HAVING
 A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4
 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS
 SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.7.
 REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO
 THE OUTSIDE AIR.
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 7) THE NEW FLOOR PLAN ON SHEET A2 SHOWS A PREFAB SHED
 FOR THE LAUNDRY EQUIPMENT AND IT IS NOT SHOWN ON THE
 SITE PLAN. IS THIS SHED GOING TO BE APPLIED FOR UNDER A
 SEPARATE PERMIT? IF IT WILL BE UNDER THIS PERMIT, ADD
 IT TO THE SITE PLAN AND SUBMIT THE SITE SPECIFIC
 ENGINEERING OR MANUFACTURED BUILDING DOCUMENTS FOR THE
 SHED. CITY AMENDMENTS FBC 107.2.1 & FBC 107.3.5.3
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  