| 2020-08-28 13:18:32 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20070889 |
| | 8/28/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) LP GAS TANK AND LP REGULATOR SPECS HAVE BEEN |
| | SUBMITTED WHICH ARE NOT RELEVANT TO THE NATURAL GAS |
| | GENERATOR INSTALLATION. I AM NOT ABLE TO SEPARATE OUT |
| | THE RELEVANT SUBMITTALS IN THE PACKAGE YOU SUBMITTED SO |
| | PLEASE SEPARATELY RESUBMIT THE DORMONT FLEX CONNECTOR |
| | AND THE PE PIPING SPECS. ONCE THOSE ARE RECEIVED THE |
| | INITIAL PACKAGE SENT WILL BE VOIDED- SECTION 107.2.1 |
| | WPB. |
| | |
| | 2) GAS SURVEY: PLEASE SUBMIT THE GENERAC MANUFACTURER'S |
| | GUIDELINES FOR INSTALLATION CLEARANCES TO VERIFY THE |
| | CLEARANCES SPECIFIED ON THE DRAWING. THE GUIDELINES CAN |
| | SUPERSEDE THE MINIMUM 10 FT. CLEARANCE TO OPERABLE |
| | OPENINGS INTO THE BUILDING PER SECTION R303.5.1 FBC |
| | RES. |
| | |
| | 3) GAS RISER: |
| | |
| | A) PROVIDE THE DELIVERY PRESSURE AT THE METER- SECTIONS |
| | G2413.2, G2413.4.1 & G2413.5 FBC RES. |
| | |
| | B) PROVIDE THE TOTAL DEVELOPED LENGTH FROM THE METER TO |
| | THE MOST REMOTE APPLIANCE- PLEASE INCLUDE THE BRANCH |
| | LINE TO THE POOL HEATER WHICH IS NOT SHOWN ON THE |
| | RISER- SECTIONS G2413.4.1 & G2413.2. |
| | |
| | C) PROVIDE THE PIPE SIZING TABLES LISTED UNDER SECTION |
| | G2413.4. PLEASE NOTE THAT THE TABLE 402.4(3) FROM THE |
| | FBC FG SUBMITTED WITH THE REGULATOR SPECS CANNOT BE |
| | USED BECAUSE PIPE SIZING SHALL BE DONE ACCORDING TO THE |
| | TABLES IN THE FBC RES. THERE IS NO RELEVANT TABLE IN |
| | THE FBC RES THAT ALLOWS THE 3.0 IN. WC PRESSURE DROP. |
| | PLEASE SEE TABLE G2413.4(1) WHICH INDICATES A TYPICAL |
| | 0.5 IN. WC PRESSURE DROP FOR RESIDENTIAL APPLIANCES, |
| | AND REFER TO SECTION G2413.5 FOR FURTHER CLARIFICATION. |
| | PLEASE NOTE THAT THE TABLES IN THE FBC FG CAN BE USED |
| | IF THE RELEVANT TABLE IS CONTAINED IN THE FBC RES SUCH |
| | AS TABLE G2413.4(1) & {402.4(2)}. |
| | |
| | 4) PLEASE RESUBMIT THE REGULATOR SPECS MARKED UP TO |
| | SHOW MODEL, PRESSURE DROP, AND SPRING SELECTIONS. IN |
| | LIEU OF MARKING UP THE SPECS, PLEASE PROVIDE THE |
| | INFORMATION ON THE RESUBMITTED RISER DRAWING- SECTIONS |
| | G2421.1 & G2421.2 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |