| | BUILDING REVIEW DENIED: |
| | |
| | 1) FBC B 109.3, THE VALUATION OF THE PROJECT APPEARS TO |
| | BE LOW. PROVIDE A BREAK DOWN OF THE VALUATION INCLUDING |
| | ALL MATERIAL, LABOR & SERVICES INVOLVED. |
| | |
| | 2) FBC B 107, PROVIDE A REPORT FROM AN ACCEPTABLE |
| | LICENSED COMPANY SHOWING THE LOCATION OF POST TENSION |
| | CABLES (X-RAYED OR OTHER ACCEPTABLE METHOD). THIS IS TO |
| | AVOID DAMAGE TO CABLES DURING PENETRATION OF SLAB. |
| | |
| | 3) FBC B 714.4.1.2, FBC B TABLE 601, PROVIDE |
| | INFORMATION OF MATERIAL TO BE USED TO SEAL THE FLOOR |
| | PENETRATIONS (2HR RATING REQUIRED). |
| | |
| | 4) FBC B 2509.2, PROVIDE INFORMATION AS TO THE TYPE OF |
| | WATER RESISTANT WALL BOARD THAT WILL BE USED IN THE WET |
| | AREAS OF THE EXTENDED SHOWER SPACE. |
| | |
| | 5) FBC B 1207.2, 1207.2 & 603.1, THE FOLLOWING TESTS |
| | ARE REQUIRED AT THE NEW FLOORING AREAS (EXISTING BATH |
| | TUB AREA). |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) : |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | NOTE: PLEASE FEEL FREE TO CONTACT ME IF YOU ARE UNSURE |
| | ABOUT AN ACCEPTABLE FLOOR UNDERLAYMENT. |
| | |