| 2020-09-28 06:34:01 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | SIGNATURE REVIEW DENIED: | | | | | | WPB AMENDMENTS TO FBC B 107.2.1, SECTION "D" OF | | | ELEVATION CERTIFICATE; PLEASE PROVIDE THE SURVEYOR'S | | | DIGITAL OR ORIGINAL PAPER SIGNED/SEALED | | | ELEVATION CERTIFICATE DROPPED OFF AT THE DROP BOX OF | | | THE BUILDING DEPARTMENT. | | | |
|