| 2021-06-17 19:04:24 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | |
| | 1) UPDATED SHEETS C5.00, C5.10 AND C6.00 SHOWING THE |
| | UPDATED FPL EASEMENT LOCATION ALONG THE SOUTH PROPERTY |
| | LINE WHICH WERE NOT RESUBMITTED WITH THIS PERMIT |
| | RESUBMITTAL. THE SAME PLANS THAT WERE SUBMITTED WITH |
| | THE MINOR AMENDMENT NEED TO BE UPLOADED. |
| | |
| | 2) 000.2 BASEMENT FLOOR LEVEL PLAN (SHEET A113) IS NOT |
| | THE MOST RECENT VERSION OF THIS PLAN AND DOES NOT |
| | REFLECT THE SAME CONDITIONS AS SHEETS A-100 AND A-100A. |
| | |
| | 3) 000.3 GROUND FLOOR SITE PLAN (SHEET A114) WAS NOT |
| | UPDATED TO REFLECT THE RELOCATED WALL BETWEEN THE MAIN |
| | SWITCHGEAR ROOM AND THE FPL VAULT THAT IS SHOWN ON |
| | SHEETS A-101, A-101A AND S-101 THAT WAS SUBMITTED WITH |
| | THE PERMIT. THIS PLAN NEEDS TO SHOW ACCURATE |
| | CONDITIONS. |
| | |
| | 4) UPDATED SHEETS A-101 AND A-101A RENUMBERED THE TWO |
| | PARKING SPACES ALONG ARKONA COURT, BUT INADVERTENTLY |
| | USED #57 TWICE AND DID NOT INCLUDE #59. ZONING STAFF |
| | REDLINED THIS AS PART OF THE APPROVAL OF THESE PLAN |
| | SHEETS. |
| | |
| | 5) THE 3D OUTDOOR MODEL VIEWS FOR THE NEW OUTDOOR |
| | SHOWER LAYOUT THAT WERE SUBMITTED WITH (AND ARE BEING |
| | APPROVED WITH) THE MINOR PLANNED DEVELOPMENT AMENDMENT |
| | WERE NOT INCLUDED WITH THE PERMIT RESUBMITTAL. THE |
| | MINOR AMENDMENT VERSION DRAWINGS MUST BE UPLOADED AS |
| | SUPPORTING DOCUMENTS WITH THIS PERMIT. |
| | |
| | 6) SHEET A-255 ENLARGED ARRIVAL COURT DOES NOT MATCH |
| | THE CURRENT ARRIVAL COURT LAYOUT APPROVED ON SHEET |
| | A-102 AND A-102A. THIS PLAN NEEDS TO SHOW ACCURATE |
| | CONDITIONS. |
| | |
| | 7) SHEET A-302 LEVEL 02 ? AMENITY LEVEL REFLECTED |
| | CEILING PLAN DOES NOT MATCH THE CURRENT POOL BATH |
| | LAYOUT APPROVED ON SHEET A-102 AND A-102A. THIS PLAN |
| | NEEDS TO SHOW ACCURATE CONDITIONS. |
| | |