Plan Review Notes
Plan Review Notes For Permit 20070795
Permit Number 20070795
Review Stop P
Sequence Number 4
Notes
Date Text
2021-05-24 12:00:35 
 1) SHT. A-771 - DETAIL #17 - THE WATER CLOSET IS SHOWN
 AS BEING 14 1/2 INCHES FROM THE ADJACENT GLASS
 PARTITION. THE WATER CLOSET SHALL BE LOCATED 18 INCHES
 FROM THE GLASS PARTITION TO THE CENTERLIINE OF THE
 WATER CLOSET PER THE FHA GUIDELINES FIG.7 (A).2ND
 REQUEST.
 2) SHT. A-772 - DETAIL #12 - THE CENTERLLINE OF THE
 WATER CLOSET SHALL BE LOCATED 18 INCHES FROM THE EDGE
 OF THE GLASS SHOWER PARTITIONPER FHA GUIDELINES FIGURE
 7 (A). 2ND REQUEST.
 3) SHT. P-501B - A FULL OPEN SHUTOF VALVE IS REQUIRED
 AT THE BASE OF THE 6 INCH RISER FROM THE DOMESTIC
 BOOSTER PUMPSPER FBC-PLUMBING SEC.606.1. 2ND REQUEST.
 4) SHT. P-502G - THERE ARE RISERS ON THIS PAGE WITH
 RISER TAGS AND NO INFORMATION IN THESE RISER TAGS.
 PROVIDE THE REQUIRED INFORMATION. WPB AMEND.TO FBC SEC.
 107.1.
 5) SHT. P-502G - THERE ARE MULTIPLE CLOUDED LOCATIONS
 ON THESE PLANS WITH NO INFORMATION NOTED.CLARIFY.
 6) SHT. P-502G - THERE ARE STILL DRAIN PIPES AND VENT
 PIPES MISSING PIPE SIZES.THERE ARE NUMEROUS ARROWS
 DRAWN ON THE PLUMBING RISER WITH NO NOTES ATTACHED THAT
 I HAVE NO IDEA WHAT THEY ARE FOR. DELETE THESE ARROW AS
 THEY OBVIOSLY DO NO GOOD AND ONLY SERVE TO CONGEST THE
 RISER DIAGRAM. ENSURE ALL DRAINS AND RISERS ARE
 SIZED.WPB AMEND. TO FBC SEC.107.1.2ND REQUEST.
 7) SHOW THE CONTINUATION POINT OF THE 3 INCH VENT FOR
 THE WATER CLOSET AND LAVATORY.2ND REQUEST.
  
 FUEL TANK/ FUEL PIPING
 8) EACH CONNECTION TO AN ABOVEGROUND TANK THROUGH WHICH
 LIQUID CAN NORMALLY FLOW SHALL BE PROVIDED WITH AN
 INTERNAL OR AN EXTERNAL VALVE LOCATED AS CLOSE AS
 PRACTICAL TO THE SHELL OF THE TANK.NFPA 30 SEC.
 22.13.1. REFER TO THE SUPPLY AND RETURN LINES TO THE
 GENERATOR.COMPLY WITH THE ABOVE COMMMENT.3RD REQUEST.
  
 THE FOLLOWING TEXT IS FROM THE NFPA 30 HANDBOOK:
 A CHECK VALVE DOES NOT SATISFY THE REQUIREMENTS OF THIS
 SECTION.
 SUBSECTION 22.13.1 REQUIRES A MANUAL OR REMOTELY
 OPERATED VALVE THAT CAN BE USED TO ISOLATE THE TANK
 FROM ITS PIPING DURING AN EMERGENCY. A CHECK VALVE
 ALONE CANNOT BE USED TO MEET THIS REQUIREMENT, ALTHOUGH
 ONE CAN BE USED IN CONJUNCTION WITH THE OPERATING
 VALVE. A WORD OF CAUTION: A CHECK VALVE IN THE INLET
 PIPELINE PREVENTS THAT PIPELINE FROM BEING USED AS AN
 EMERGENCY OUTLET. IN A FIRE EMERGENCY, PUMPING LIQUID
 FROM A FIRE-INVOLVED TANK TO ANOTHER TANK OUTSIDE THE
 FIRE AREA CAN BE PRACTICAL.
 BECAUSE REPAIR OR MAINTENANCE OF INTERNAL VALVES
 USUALLY REQUIRES THAT TANKS BE EMPTIED, THEY ARE SELDOM
 USED ON LARGER TANKS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  