| Date |
Text |
| 2021-05-24 12:00:35 | |
| | 1) SHT. A-771 - DETAIL #17 - THE WATER CLOSET IS SHOWN |
| | AS BEING 14 1/2 INCHES FROM THE ADJACENT GLASS |
| | PARTITION. THE WATER CLOSET SHALL BE LOCATED 18 INCHES |
| | FROM THE GLASS PARTITION TO THE CENTERLIINE OF THE |
| | WATER CLOSET PER THE FHA GUIDELINES FIG.7 (A).2ND |
| | REQUEST. |
| | 2) SHT. A-772 - DETAIL #12 - THE CENTERLLINE OF THE |
| | WATER CLOSET SHALL BE LOCATED 18 INCHES FROM THE EDGE |
| | OF THE GLASS SHOWER PARTITIONPER FHA GUIDELINES FIGURE |
| | 7 (A). 2ND REQUEST. |
| | 3) SHT. P-501B - A FULL OPEN SHUTOF VALVE IS REQUIRED |
| | AT THE BASE OF THE 6 INCH RISER FROM THE DOMESTIC |
| | BOOSTER PUMPSPER FBC-PLUMBING SEC.606.1. 2ND REQUEST. |
| | 4) SHT. P-502G - THERE ARE RISERS ON THIS PAGE WITH |
| | RISER TAGS AND NO INFORMATION IN THESE RISER TAGS. |
| | PROVIDE THE REQUIRED INFORMATION. WPB AMEND.TO FBC SEC. |
| | 107.1. |
| | 5) SHT. P-502G - THERE ARE MULTIPLE CLOUDED LOCATIONS |
| | ON THESE PLANS WITH NO INFORMATION NOTED.CLARIFY. |
| | 6) SHT. P-502G - THERE ARE STILL DRAIN PIPES AND VENT |
| | PIPES MISSING PIPE SIZES.THERE ARE NUMEROUS ARROWS |
| | DRAWN ON THE PLUMBING RISER WITH NO NOTES ATTACHED THAT |
| | I HAVE NO IDEA WHAT THEY ARE FOR. DELETE THESE ARROW AS |
| | THEY OBVIOSLY DO NO GOOD AND ONLY SERVE TO CONGEST THE |
| | RISER DIAGRAM. ENSURE ALL DRAINS AND RISERS ARE |
| | SIZED.WPB AMEND. TO FBC SEC.107.1.2ND REQUEST. |
| | 7) SHOW THE CONTINUATION POINT OF THE 3 INCH VENT FOR |
| | THE WATER CLOSET AND LAVATORY.2ND REQUEST. |
| | |
| | FUEL TANK/ FUEL PIPING |
| | 8) EACH CONNECTION TO AN ABOVEGROUND TANK THROUGH WHICH |
| | LIQUID CAN NORMALLY FLOW SHALL BE PROVIDED WITH AN |
| | INTERNAL OR AN EXTERNAL VALVE LOCATED AS CLOSE AS |
| | PRACTICAL TO THE SHELL OF THE TANK.NFPA 30 SEC. |
| | 22.13.1. REFER TO THE SUPPLY AND RETURN LINES TO THE |
| | GENERATOR.COMPLY WITH THE ABOVE COMMMENT.3RD REQUEST. |
| | |
| | THE FOLLOWING TEXT IS FROM THE NFPA 30 HANDBOOK: |
| | A CHECK VALVE DOES NOT SATISFY THE REQUIREMENTS OF THIS |
| | SECTION. |
| | SUBSECTION 22.13.1 REQUIRES A MANUAL OR REMOTELY |
| | OPERATED VALVE THAT CAN BE USED TO ISOLATE THE TANK |
| | FROM ITS PIPING DURING AN EMERGENCY. A CHECK VALVE |
| | ALONE CANNOT BE USED TO MEET THIS REQUIREMENT, ALTHOUGH |
| | ONE CAN BE USED IN CONJUNCTION WITH THE OPERATING |
| | VALVE. A WORD OF CAUTION: A CHECK VALVE IN THE INLET |
| | PIPELINE PREVENTS THAT PIPELINE FROM BEING USED AS AN |
| | EMERGENCY OUTLET. IN A FIRE EMERGENCY, PUMPING LIQUID |
| | FROM A FIRE-INVOLVED TANK TO ANOTHER TANK OUTSIDE THE |
| | FIRE AREA CAN BE PRACTICAL. |
| | BECAUSE REPAIR OR MAINTENANCE OF INTERNAL VALVES |
| | USUALLY REQUIRES THAT TANKS BE EMPTIED, THEY ARE SELDOM |
| | USED ON LARGER TANKS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |