Date Text
2021-04-02 09:11:301) SHT. A-224 - THE LOCATION OF THE SHOWER HEAD AND
 SHOWER CONTROLS FOR THE FHA BATHROOM DO NOT CORRELATE
 WITH THE LOCATION OF THE HEAD AND CONTROLS SHOWN ON
 SHT. A-772, DEAIL #12. CLARIFY.
 2) SHT. A-243A - WOMEN'S ADA TOILET ROOM - THE LAVATORY
 IN THE ACCESSIBLE TOILET ROOM IS SHOWN ENCROACHING INTO
 THE CLEAR FLOOR SPACE FOR THE WATER CLOSET. THE
 LAVATORY CANNOT ENCROACH INTO THE CLEAR FLOOR SPACE.
 2) SHT. A-770 - DETAIL #1 - THE WATER CLOSET IN THE FHA
 BATHRROM SHALL BE LOCATED 18 INCHES FROM THE ADJACENT
 WALL TO THE CENTERLINE OF THE WATER CLOSET PER THE FHA
 GUIDELINES FIG.7 (A).
 3) SHT. A-771 - DETAIL #17 - THE WATER CLOSET IS SHOWN
 AS BEING 14 1/2 INCHES FROM THE CENTERLINE OF THE WATER
 CLOSET TO THE GLASS PARTITION. THE WATER CLOSET SHALL
 BE LOCATED 1 FOOT 6 INCHES FROM THE GLASS PARTITION TO
 THE CENTERLINE OF THE WATER CLOSET PER FHA GUIDELINES
 FIG.7 (A). I HAVE CONFIRMED THIS WITH A FAIR HOUSING
 FIRST REPRESENTATIVE WHO IS THE TECHNICAL ADVISORY
 ENTITY FOR HUD.
 4) SHT. A-772 - DETAIL #12 - THE CENTERLINE OF WATER
 CLOSET SHALL BE LOCATED 1 FOOT AND 6 INCHES FRROM THE
 EDGE OF THE GLASS SHOWER PARITION PER THE FHA
 GUIDELINES FIGURE 7 (A).
 5) SHT. A-774 - DETAIL #7 - THE WATER CLOSET LOCATED
 WITHIN THE TOILET COMPARTMENT SHALL BE LOCATED A
 MINIMUM 18 INCHES FROM THE ADJACENT WALL PER THE FHA
 GUIDELINES FIGURE 7 (A).
 6) SHT. P-241 & SHT.P-707 - THE VENTING FOR THE GREASE
 TRAP SHALL COMPLY WITH FBC-PLUMBING SEC.905.4. DEATAIL
 #7 ON SHT. P-707 APPEARS TO SHOW THE VENTS OFFSETTING
 HORIZONTALLY BELOW THE FLOOD LEVEL RIM OF THE
 INTERCEPTOR.EVERY DRY VENT SHALL RISE VERTICALLY TO A
 POINT NOT LESS THAN 6 INCHES ABOVE THE FLOOD LLEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
 7) SHT. P-501B - THE BACKFLOW DEVICES FOR THE COOLING
 TOWER AND IRRIGATION SYSTEM SHALL BE LEAD FREE REDUCED
 PRESSURE ZONE BACKFLOWS PER THE CITY OF WPB CROSS
 CONNECTION CONTROL MANUAL. 2ND. REQUEST.
 8) SHT. P-501B - A FULL OPEN SHUTOFF VALVE IS REQUIRED
 AT THE BASE OF THE 6 INCH RISER FROM THE DDOMESTIC
 PUMPS PER FBC-PLUMBING SEC.606.1 (4).
 8) SHT. P-503A - THE TOP OF RISER ST/6 IS CUT OFF AND
 CANNOT BE REVIEWED. SUBMIT THE ENTIRE RISER FOR REVIEW.
 9) SHT. P-502G - PIPE SIZES ARE MISSING ON THE
 HORIZONTAL SANITARY LINE FROM THE DOG WASH AND THERE
 ARE VENT SIZES MISSING FROM THE VENT PIPING IN THIS
 AREA.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT. P-502G - SHOW THE CONTINUATION POINT OF THE 3
 INCH VENT FOR THE WATER CLOSET & LAVATORY & FLOOR
 DRAINS ON THE RISER DIAGRAM.WPB AMEND. TO FBC SEC.
 107.2.1.
 11) SHT. P-502G - SIZE THE HORIZONTAL DRAIN AND
 VERTICAL SECTION FOR RISERS S3 & S/6. WPB AMEND. TO FBC
 SEC. 107.2.1.
 12) SHT. P- 502G - THERE IS A 4 INCH FLOOR DRAIN
 DISCHARGING INTO THE SANITARY EJECTOR BUT THIS LINE IS
 NOT SHOWN ON SHT. P-100B. WHAT DOES THIS FLOOR DRAIN
 SERVE? CLARIFY ON THE PLANS.
 11) SHT. P-5002G - THERE IS A NOTE AT THE 12 INCH
 SANITARY LINE THAT STATES "REFER TO CIVIL DRAWING FOR
 CCONTINUATION." PLACE THE SPECIFIC CIVIL DRAWING NUMBER
 ON THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHT. P-502G - SIZE RISER # S/A.WPB AMEND. TO FBC
 SEC. 107.2.1.
 13) SHT. P-502G - THERE ARE VENT AND PIPE SIZES MISSING
 ON THE RISER DIAGRAM FROM ONE SIDE OF THE SHEET TO THE
 OTHER. SSIZE ALL MISSING SECTIONS OF SANITARY PIPING
 AND VENTS. WPB AMEND. TO FBC 107.2.1.
 14) SHT. P-707 - DETAIL #7 - CLEARLY IDENTIFY THE
 SAMPLING PORT ON THE DETAIL AND THE SIZE OF THE
 SAMPLING PORT. THE MINIMUM DIAMTER OPENING SHLL BE 4
 INCHES IN DIAMETER.
 15) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GREASE
 INTERCEPTOR (MAKE, MODEL, CAPACITY, ETC.). WPB AMEND.
 TO FBC SEC. 107.2.1.
 16) SHT P707 - DETAIL 7 - PLACE THE FOLLWING
 INFORMATION ON THE PLANS: 2ND REQUEST.
 A) THE TYPE AND NUMBER OF PLUMBING FIXTURES DISCHARGING
 INTO THE INTERCEPTOR
 B) THE STANDARD BEING USED FOR THE FLOW CALCULATIONS
 DISCHARGING INTO THE INTERCEPTOR.
  
 FUEL TANK/FUEL PIPING
 17) SUBMIT SPECIFICATIONS/INFORMATION/ INSTALLATION
 MANUAL ON THE FUEL POLISHING SYSTEM. WPB AMEND. TO FBC
 SEC. 107.2.1.2ND REQUEST.
 18) SHT. P-242 - THE SUPPLY AND RETURN PIPING TO THE
 FUEL POLISHING SYSTEM AND THE FUEL POLISHING UNIT IS
 NOT SHOWN ON THE PIPING DIAGRAMS ON SHT. P-708.
 CLARIFY.
 19) SOME OF THE PREVIOUS FUEL PIPING REVIEW COMMENTS
 HAVE NOT BEEN ADDRESSED. REFER TO PREVIOUS COMMENTS
 #55, 56, 61, AND 62. SUBMIT INFORMATION COMPLYING WITH
 THESE COMMENTS.PREVIOUS COMMENTS #51, 53, AND 54 WILL
 BE PROVISOS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW