| 2021-04-02 09:11:30 | 1) SHT. A-224 - THE LOCATION OF THE SHOWER HEAD AND |
| | SHOWER CONTROLS FOR THE FHA BATHROOM DO NOT CORRELATE |
| | WITH THE LOCATION OF THE HEAD AND CONTROLS SHOWN ON |
| | SHT. A-772, DEAIL #12. CLARIFY. |
| | 2) SHT. A-243A - WOMEN'S ADA TOILET ROOM - THE LAVATORY |
| | IN THE ACCESSIBLE TOILET ROOM IS SHOWN ENCROACHING INTO |
| | THE CLEAR FLOOR SPACE FOR THE WATER CLOSET. THE |
| | LAVATORY CANNOT ENCROACH INTO THE CLEAR FLOOR SPACE. |
| | 2) SHT. A-770 - DETAIL #1 - THE WATER CLOSET IN THE FHA |
| | BATHRROM SHALL BE LOCATED 18 INCHES FROM THE ADJACENT |
| | WALL TO THE CENTERLINE OF THE WATER CLOSET PER THE FHA |
| | GUIDELINES FIG.7 (A). |
| | 3) SHT. A-771 - DETAIL #17 - THE WATER CLOSET IS SHOWN |
| | AS BEING 14 1/2 INCHES FROM THE CENTERLINE OF THE WATER |
| | CLOSET TO THE GLASS PARTITION. THE WATER CLOSET SHALL |
| | BE LOCATED 1 FOOT 6 INCHES FROM THE GLASS PARTITION TO |
| | THE CENTERLINE OF THE WATER CLOSET PER FHA GUIDELINES |
| | FIG.7 (A). I HAVE CONFIRMED THIS WITH A FAIR HOUSING |
| | FIRST REPRESENTATIVE WHO IS THE TECHNICAL ADVISORY |
| | ENTITY FOR HUD. |
| | 4) SHT. A-772 - DETAIL #12 - THE CENTERLINE OF WATER |
| | CLOSET SHALL BE LOCATED 1 FOOT AND 6 INCHES FRROM THE |
| | EDGE OF THE GLASS SHOWER PARITION PER THE FHA |
| | GUIDELINES FIGURE 7 (A). |
| | 5) SHT. A-774 - DETAIL #7 - THE WATER CLOSET LOCATED |
| | WITHIN THE TOILET COMPARTMENT SHALL BE LOCATED A |
| | MINIMUM 18 INCHES FROM THE ADJACENT WALL PER THE FHA |
| | GUIDELINES FIGURE 7 (A). |
| | 6) SHT. P-241 & SHT.P-707 - THE VENTING FOR THE GREASE |
| | TRAP SHALL COMPLY WITH FBC-PLUMBING SEC.905.4. DEATAIL |
| | #7 ON SHT. P-707 APPEARS TO SHOW THE VENTS OFFSETTING |
| | HORIZONTALLY BELOW THE FLOOD LEVEL RIM OF THE |
| | INTERCEPTOR.EVERY DRY VENT SHALL RISE VERTICALLY TO A |
| | POINT NOT LESS THAN 6 INCHES ABOVE THE FLOOD LLEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | 7) SHT. P-501B - THE BACKFLOW DEVICES FOR THE COOLING |
| | TOWER AND IRRIGATION SYSTEM SHALL BE LEAD FREE REDUCED |
| | PRESSURE ZONE BACKFLOWS PER THE CITY OF WPB CROSS |
| | CONNECTION CONTROL MANUAL. 2ND. REQUEST. |
| | 8) SHT. P-501B - A FULL OPEN SHUTOFF VALVE IS REQUIRED |
| | AT THE BASE OF THE 6 INCH RISER FROM THE DDOMESTIC |
| | PUMPS PER FBC-PLUMBING SEC.606.1 (4). |
| | 8) SHT. P-503A - THE TOP OF RISER ST/6 IS CUT OFF AND |
| | CANNOT BE REVIEWED. SUBMIT THE ENTIRE RISER FOR REVIEW. |
| | 9) SHT. P-502G - PIPE SIZES ARE MISSING ON THE |
| | HORIZONTAL SANITARY LINE FROM THE DOG WASH AND THERE |
| | ARE VENT SIZES MISSING FROM THE VENT PIPING IN THIS |
| | AREA.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10) SHT. P-502G - SHOW THE CONTINUATION POINT OF THE 3 |
| | INCH VENT FOR THE WATER CLOSET & LAVATORY & FLOOR |
| | DRAINS ON THE RISER DIAGRAM.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 11) SHT. P-502G - SIZE THE HORIZONTAL DRAIN AND |
| | VERTICAL SECTION FOR RISERS S3 & S/6. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 12) SHT. P- 502G - THERE IS A 4 INCH FLOOR DRAIN |
| | DISCHARGING INTO THE SANITARY EJECTOR BUT THIS LINE IS |
| | NOT SHOWN ON SHT. P-100B. WHAT DOES THIS FLOOR DRAIN |
| | SERVE? CLARIFY ON THE PLANS. |
| | 11) SHT. P-5002G - THERE IS A NOTE AT THE 12 INCH |
| | SANITARY LINE THAT STATES "REFER TO CIVIL DRAWING FOR |
| | CCONTINUATION." PLACE THE SPECIFIC CIVIL DRAWING NUMBER |
| | ON THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 12) SHT. P-502G - SIZE RISER # S/A.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 13) SHT. P-502G - THERE ARE VENT AND PIPE SIZES MISSING |
| | ON THE RISER DIAGRAM FROM ONE SIDE OF THE SHEET TO THE |
| | OTHER. SSIZE ALL MISSING SECTIONS OF SANITARY PIPING |
| | AND VENTS. WPB AMEND. TO FBC 107.2.1. |
| | 14) SHT. P-707 - DETAIL #7 - CLEARLY IDENTIFY THE |
| | SAMPLING PORT ON THE DETAIL AND THE SIZE OF THE |
| | SAMPLING PORT. THE MINIMUM DIAMTER OPENING SHLL BE 4 |
| | INCHES IN DIAMETER. |
| | 15) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GREASE |
| | INTERCEPTOR (MAKE, MODEL, CAPACITY, ETC.). WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 16) SHT P707 - DETAIL 7 - PLACE THE FOLLWING |
| | INFORMATION ON THE PLANS: 2ND REQUEST. |
| | A) THE TYPE AND NUMBER OF PLUMBING FIXTURES DISCHARGING |
| | INTO THE INTERCEPTOR |
| | B) THE STANDARD BEING USED FOR THE FLOW CALCULATIONS |
| | DISCHARGING INTO THE INTERCEPTOR. |
| | |
| | FUEL TANK/FUEL PIPING |
| | 17) SUBMIT SPECIFICATIONS/INFORMATION/ INSTALLATION |
| | MANUAL ON THE FUEL POLISHING SYSTEM. WPB AMEND. TO FBC |
| | SEC. 107.2.1.2ND REQUEST. |
| | 18) SHT. P-242 - THE SUPPLY AND RETURN PIPING TO THE |
| | FUEL POLISHING SYSTEM AND THE FUEL POLISHING UNIT IS |
| | NOT SHOWN ON THE PIPING DIAGRAMS ON SHT. P-708. |
| | CLARIFY. |
| | 19) SOME OF THE PREVIOUS FUEL PIPING REVIEW COMMENTS |
| | HAVE NOT BEEN ADDRESSED. REFER TO PREVIOUS COMMENTS |
| | #55, 56, 61, AND 62. SUBMIT INFORMATION COMPLYING WITH |
| | THESE COMMENTS.PREVIOUS COMMENTS #51, 53, AND 54 WILL |
| | BE PROVISOS. |
| | |