| 2020-12-16 08:58:46 | 1) SHT. G-10 - 010.20180831 - PLUMBING FIXTURE SCHEDULE |
| | - TAG #F25 REFERS TO A KOHLER WALL-MOUNT BATHROOM SINK |
| | & FAUCET WITH CROSS HANDLES. THESE HANDLES DO NOT MEET |
| | THE INTENT OF ANSI A117.1-1986 SECS.4.19.5 & 4.25.4. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THIS ITEM. |
| | NOTE: BLADE HANDLES ARE AVAILABLLE FROM THE |
| | MANUFACTURER FOR THIS ITEM. THE RESPONSE NARRATIVE |
| | REFERS TO A CUT-SHEET FROM KOHLER. THERE IS NO ATTACHED |
| | CUT SHEET. THE HANDLES SHALL BE CHANGED TO BLADE |
| | HANDLES TO COMPLY WITH THE FLORIDA ACCESSIBILITY |
| | CODE.INDICATE THIS ON THE IXTURE SCHEDULE. 2ND REQUEST. |
| | 2) SHT. A-224A - UNIT "E" - DETAIL #2 STILL REFERS TO |
| | DETAIL #12 ON SHT.A-772. SHT. A-772 IS NOT INCLUDED IN |
| | THIS SUBMITTAL.THE DETAIL # AND REFERENCED PLAN NEEDS |
| | TO BE CORRECTED. 2ND REQUEST. |
| | 3) SHT. A-227A & A-771A - THE WALL NEXT TO THE WATER |
| | CLOSET CANNOT EXCEED 24 INCHES PER THE FAIR HOUSING ACT |
| | DESIGN MANUAL PAGE 7.43. THIS LAYOUT WITH THE SHOWER |
| | NEXT TO THE WATER CLOSET WILL NOT COMPLY |
| | 4) SHT. A-243A - THE MEN'S AND WOMEN'S ADA SHOWER - THE |
| | SHOWER STALL SIZE AND CLEAR FLOOR SPACE SHALL COMPLY |
| | WITH ANSI A117.1-1986 SECS.4.21.1, 4.21.2, 4.21.4, |
| | 4.21.5,4.21.6, & 4.21.8. AS DESIGNED, THESE SHOWERS DO |
| | NOT COMPLY WITH THE SIZE REQUIREMENTSAS STATED IN THE |
| | ANSI DOCUMENT. |
| | 5) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE |
| | SAND/OIL INTERCEPTOR. THE INTERCEPTOR SHALL COMPLY WITH |
| | FBC-PLUMBING SECS.1003.4.2, 1003.4.2.1. DETAIL #9 IS |
| | FOR THE STORM SUMPS, NOT A SAND/OIL INTERCEPTOR. 2ND |
| | REQUEST. |
| | 6) SHT.A-626 - DETAILS #1 & #2 - PROVIDE THE DIMENSIONS |
| | OF THE ALUMINUM TUBE SCUPPER DRAINS FOR THE |
| | BALCONY.THERE ARE NO DIMENSIONS SHOWN ON THE PLANS. 2ND |
| | REQUEST. |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HAIR |
| | INTERCEPTOR. THE SPECIFICATIONS SHALL SHOW THE LISTING |
| | ORGANIZATION APPROVAL FOR THE UNIT. THE MODEL NUMBER |
| | HAS BEEN SUBMITTED BUT NOT THE SPECIFICATIONS AS |
| | PREVIOUSLY REQUESTED. 2ND REQUEST.FBC-PLUMBING |
| | SEC.1003.2, WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) DOCUMENTATION FROM MANNY GONZALEZ REGARDING THE |
| | DISCHARGE OF THE POOL WATER TO THE SANITARY SYTEM SHALL |
| | BE SUBMITTED AND ALSO REGARDING THE DISCHARGE OF THE |
| | POOL NON-CONTAMINATED WATER TO THE STORM SYSTEM. |
| | 9) THE CONDENSATE LINE SHOWN ON SHT.P-100B IS NOT SHOWN |
| | ON SHT. P-503B. REFER TO GRIDLINE GQ BETWEEN G18-G21. |
| | 10) SUBMIT A REVISED CONDENSATE RISER FOR THE ADDED |
| | CONDENSATE DRAINS AND TAG THESE RISERS. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 11) SUBMIT A STORM RISER DIAGRAM FOR THE ADDED TERRACE |
| | DRAINS FOR THE AFFECTED UNITS. REFER TO SHTS. P-107, |
| | P-108 & P-109. |
| | 12) SHT. P-100B - SANITARY PIPING ISOMETRIC - THE |
| | LAYOUT OF RISERS S/2, S/3, S/4 & S/5 DOES NOT CORRELATE |
| | WITH THE LAYOUT ON SHT. P-506. CLARIFY. |
| | 13) SHT. P-100B - SHOWS A SANITARY RISER LABELED S/A |
| | BUT THIS RISER IS NOT SHOWN ON SHT. P-506. CLARIFY. |
| | WHAT DOES THIS RISER SERVE? |
| | 14) SHT. P-100B - RISERS S/9, S/18, S/15, S/16 ARE |
| | SHOWN ON THE SANITARY RISER ON SHT. P-506 BUT NOT ON |
| | SHT. P-100B. CLARIFY. |
| | 15) SHT. P-100B - THE LAYOUT OF THE SANITARY RISERS ON |
| | THE FLOOR PLAN DOES NOT CORRELATE WITH THE LAYOUT ON |
| | THE SANITARY RISER ON P- 506. |
| | 16) SHT. P-100B - THE PIPING FROM THE SANITARY EJECTOR |
| | BY COL. G10 BETWEEN GF-GH IS NOT SHOWN ON THE SANITARY |
| | RISER ON SHT. P-502G OR P-506. CLARIFY. |
| | 17) SHT. P-102B - THERE IS A CLOUDED NOTE ON THE PLAN |
| | THAT READS " PIPES CONTINUE ON SHEET P-102B." THIS NOTE |
| | APPEARS TO BE A TYPO BECAUSE THE NOTE IS ON P-102B. AND |
| | THE MATCH LINE NOTE REFERS TO SHT. 102A. |
| | 18) SHT. P-109 - THE 3 INCH DD (255 SF) IS NOT SHOWN ON |
| | ANY O THE STORM RISERS ON SHT.P-503A. CLARIFY. IF THIS |
| | DRAIN IS LOCATED ON ANOTHER RISER ON ANOTHER PAGE, |
| | PLACE A NOTE ON THE FLOOR PLAN WITH THE INFORMATION. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 19) SHTS. P-107, P-108 & P-109 - PLACE A NOTE ON THESE |
| | PLANS WITH THE SHEET INFORMATION AS TO WHERE THE STORM |
| | RISERS FOR THE TERRACE DRAINS CAN BE FOUND. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 20) THE SANITARY ISOMETRICS FOR THE ENLARGED UNIT PLANS |
| | (A,B, C, D, E, F, G) SHOW TWO WASHING MACHINES |
| | DISCHARGING INTO A DOUBLE PATTERN FITTING. DOUBLE |
| | PATTERN SANITARY TEE PATTERN FITTINGS SHALL NOT RECEIVE |
| | THE DISCHARGE OF FIXTURES OR APPLIANCES WITH PUMPING |
| | ACTION DISCHARGE PER FBC-PLUMBING SEC.706.3. REFER TO |
| | SHTS. P-220, P-221, P-222, P-223, P-224. |
| | 21) SHT. P-223 - SANITARY PIPING ISOMETRICS - TWO |
| | WASHING MACHINES ARE SHOWN DISCHARGING INTO THE SAME |
| | FIXTURE DRAIN. THE WASHING MACHINES SHALL CONNECT |
| | SEPARATELY TO THE STACK AND NOT THROUGH A DOUBLE |
| | PATTERN FITTING.FBC-PLUMBING SEC.706.3. |
| | 22) SHT. P-224 - THERE ARE TWO WASHING MACHINES SHOWN |
| | ON THE SANITARY RISER BUT ONLY ONE SHOWN ON THE WATER |
| | RISER. CLARIFY. 2ND REQUEST. |
| | 23) THE ISLAND VENT FOR THE KITCHEN SINK ON THE THE |
| | ENLARGED PLUMBING FLOOR PLANS (A,B, C, D, E, F, G) |
| | SHALL BE INSTALLED IN ACCORDANCE WITH FBC-PLUMBING |
| | SECS. 916.1 - 916.3.IN ADDITION, CLEANOUTS SHALL BE |
| | PROVIDED IN THE ISLAND FIXTURE VENT TO PERMIT RODDING |
| | OF ALL VENT PIPING LOCATED BELOW THE FLOOD LEVEL RIM OF |
| | THE FIXTURES. AS DRAWN, THE ISLAND VENT DOES NOT COMPLY |
| | WITH THE NOTED CODE SECTIONS.REFER TO SHTS. P-220, |
| | P-221, P-222, P-223, P-224. |
| | 24) SHT. P-241 - SANITARY PIPING ISOMETRIC DINING AREA |
| | - THE VENTING FOR THE GREASE TRAP DOES NOT APPEAR TO |
| | COMPLY WITH FBC-PLUMBING SEC.905.4. CLARIFY. |
| | 25) SHT. P-242 - DETAIL #3 - NOTE THE TYPE OF BACKFLOW |
| | PREVENTION DEVICE TO BE INSTALLED ON THE DUPLEX AND |
| | TRIPLEX WATER TREATMENT SYSTEMS. COMPLY WITH |
| | FBC-PLUMBING TABLE 608.1. |
| | 26) SHT.P-242 - DETAIL 31 - A REDUCED PRESURE ZONE |
| | VALVE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED ON |
| | THE COOLING TOWER MAKE-UP WATER AND ALSO ON THE 1 1/2 |
| | INCH CW FOR HVAC USE. |
| | 27) THE WATER SHUTOFF VALVES LOCATED IN THE WASHING |
| | MACHINE DRAIN BOX SHALL BE PROVIDED WITH ACCESS PER |
| | FBC-PLUMBING SEC.606.3. THE SHUTOFF VALVES SHALL BE |
| | ABLE TO BE OPERATED WITHIN REACH WITHOUT MOVING THE |
| | APPLIANCE. |
| | 28) SHT. P-501B - A PARTIAL DOMESTIC WATER RISER |
| | DIAGRAM HAS BEEN SUBMITTED. CLARIFY. IT APPEARS THAT |
| | THE WATER DISTRIBUTION SYSTEM IS A DOWNFEED SYSTEM. A |
| | FULLL OPEN SHUTOFF VALVE IS REQUIRED ON THE TOP OF |
| | EVERY WATERDOWNFEED PIPE PER FBC-PLUMBING SEC.606..1 |
| | (5). SUBMIT A COMPLETE WATER RISER FOR REVIEW. |
| | 29) SHT. P-501B - THE BACKFLOW DEVICE FOR THE SWIMMING |
| | POOL AND THE COOLING TOWER AND IRRIGATION SYSTEM SHALL |
| | BE REDUCED PRESSURE ZONE BACKFLOWS AND SHALL BE LEAD |
| | FREE PER THE CITY OF WPB CROSS-CONNECTION CONTROL |
| | MANUAL. |
| | 30) SHT. P-502G - RISER TAGS ARE MISSING FROM THE |
| | SANITARY RISERS. WPB AMEND. TO FBC SEC. 107.2.1.THERE |
| | ARE PIPE SIZES AND VENT SIZES MISSING, VENTS HAVE NO |
| | RISER TAGS, THE SLOPE OF THE PIPE IS MISSING AND THE |
| | CONTINUATION POINTS OF VENTS ARE NOT SHOWN/IDENTIFIED. |
| | 31) SHTS. P-503A, P-503B & P-503C - PLACE A NOTE ON |
| | THESE DRAWINGS & RISER DIAGRAMS IDENTIFYING THE PLAN |
| | VIEW SHEETS THAT ARE APPLICABLE TO THESE RISES. I COULD |
| | NOT FIND A PLAN VIEW LABELED "PODIUM EAST" OR "PODIUM |
| | WEST". WPB AMEND. TO FBC SEC. 107.2.1. |
| | 32) SHTS. P-503A, P-503B & P-503C - SHOW THE SLOPE OF |
| | THE HORIZONTAL STORM DRAIN PIPING. THE SLOPE IS ONLY |
| | SHOWN AT SEVERAL SECTIONS OF THE RISER DIAGRAMS. IF THE |
| | INTENT IS TO HAVE ALL PIPING SLOPED AT 1/8 INCH PER |
| | FOOT, PLACE A NOTE TO THIS EFFECT ON ALL THREE SHEETS. |
| | WPB AMEND TO FBC SEC.107.2.1. |
| | 33)SHT. P-502G - RISER TAGS ARE MISSING FROM THE |
| | SANITARY RISERS. WPB AMEND. TO FBC SEC. 107.2.1.THERE |
| | ARE PIPE SIZES AND VENT SIZIES MISSING, VENTS HAVE NO |
| | RISER TAGS, THE SLOPE OF THE PIPE IS MISSIN AND THE |
| | CONTINUATION POINTS OF VENTS ARE NOT SHOWN/IDENTIFIED. |
| | 34) SHT. P-503B - IDENTIFY THE CONDENSATE DRAINS ON THE |
| | RISER AND SIZE THE CONDENSATE DRAINS.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 35) SHT. P503B - PLACE A NOTE ON THE DRAWING "SEE |
| | DRAWING P-100B FOR PLAN VIEW." WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 36) SHT. P-503B - A 4 INCH STORM LINE IS MISSING FROM |
| | THE RISER DIAGRAM. REFER TO COL. LINE G9 BETWEEN COLS. |
| | GJ- GR. THERE ARE ALSO PLANTER DRAINS CALLED OUT ON TH |
| | RISER BUT PIPING IS NOT SHOWN. CLARIFY. |
| | 37) SHT. P-503B - SIZE THE HORIZONTAL STORM DRAIN THAT |
| | IS DISCHARGING INTO THE SAND INTERCEPTOR AND THE TOTAL |
| | GPM'S. |
| | 38) SHT. P-503B - THERE ARE NUMEROUS SECTIONS OF PIPING |
| | WITH NO PIPE SIZES. THERE IS ALSO A SECTION OF STORM |
| | PIPING ON THE RIGHT SIDE OF THE SHEET THAT SHOWS A 4 |
| | INCH GD THAT IS NOT CONNECTED TO THE SYSTEM AND OTHER |
| | SECTIONS IN THE SAME AREA AND LOWER CENTER WITH NO |
| | CONTINUATION POINTS. |
| | 39) SHTS.P-503B & P-503C - THE PLANS NOTE " REFER TO |
| | CIVIL DRAWINGS FOR CONTINUATION." PLACE THE SPECIFIC |
| | CIVIL DRAWING NUMBER ON THE RISERS WHERE THE STORM |
| | DRAIN CAN BE FOUND. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 40) SHT. P-506 - THERE ARE ADDITIONAL RISERS ( 4" W UP, |
| | 3" W UP, ) SHOWN ON SHT. P-100B BETWEEN COLS.G8-G11 AND |
| | GA-GB THAT ARE NOT SHOWN ON THE SANITARY PIPING |
| | ISOMETRIC ON SHT. P-506. CLARIFY. |
| | 41) SHT. P-506 - THERE ARE THREE STORM DRAINAGE PIPING |
| | ISOMETRICS WITH NO RISER TAGS. TAG ALL THE RISERS FOR |
| | IDENTIFICATION. WPB AMEND. TO FBC SEC. 107.2.1. DO THE |
| | SAME FOR THE DOWNSPOUT ISOMETRIC AND SHOW THE GPM'S |
| | DISCHARGING INTO EACH RISER & DOWNSPOUT. COMPLY WITH |
| | FBC-PLUMBING TABLES 1106.2 & 1106..3. |
| | 42) SHT. P-506 - IDENTIFY THE SPECIFIC PLAN SHEET THAT |
| | EACH RISER CORRESPONDS WITH. IT IS EXTREMELY DIFFICULT |
| | TO LOCATE THESE RISERS ON THE PLAN SHEETS IN ORDER TO |
| | SCHECK THE LAYOUT AND LOCATION.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 43) SHT. P-506 - SANITARY ISOMETRIC - SHOW THE SLOPE OF |
| | THE PIP ON THE RISER. COMPLY WITH FBC-PLUMBING SEC. |
| | 704.1 & TABLE 704.1. |
| | 44) SHT. P-506 - STORM DRAINAGE PIPING ISOMETRIC WITH |
| | RISER TAGS - THE LAYOUT OF THE STORM PIPING ON THE |
| | RISER DIAGRAM DOES NOT CORRRELATE WITH THE PLAN VIEW |
| | LAYOUT ON SHT. P-100B. |
| | 45) SHT. P-506 - IDENTIFY/ LABEL EACH RISER WITH EITHER |
| | LETTER OR NUMERICAL CHARACTERS . WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 46) BACKFLOW PREVENTION DEVICES OTHER THAN THE DUAL |
| | CHECK VALVES SHALL BE PERMITTED UNDER A SEPARATE PERMIT |
| | PER THE CITY OF WPB CROSS- CONNECTION CONTROL MANUAL |
| | SEC. (B) (5). |
| | 47) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION |
| | INSTRUCTIONS FOR THE STEAM GENERATOR. REFER TO WATER |
| | ISOMETRIC FOR THE SPA AND CHANGING AREA ON SHT. P-240. |
| | 48) SHT.P- 601 - THERMOSTATIC MIXING VALVE SCHEDULE |
| | SHOWS THE VALVES COMPLYING WITH ASSE 1017. THE |
| | FBC-PLUMBING SEC.607.1.2 REQUIRES TEMPERED WATER TO BE |
| | SUPPLIED THROUGH A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 AND SHALL LIMIT THE TEMPERED |
| | WATER TO A MAXIMUM OF 110 DEGREES. |
| | 49) SHT. P-707 - SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND SIZING CALCULATIONS FOR THE GREASE INTERCEPPTOR. |
| | THE SUBMITTED SIZING CALCULATIONS ARE VAGUE AND |
| | INCOMPLETE. |
| | A) WHAT FIXTURES ARE DISCHARGNG INTO THE INTERCEPTOR |
| | AND HOW MANY? THE PLANS SHOW 2 SINKS AND 2 DISHWASHERS. |
| | B) WHAT STANDARD IS BEING USED FOR THE SIZING OF THE |
| | INTERCEPTOR? |
| | C) A SAMPLING PORT IS REQUIRED ON THE OUTLET OF THE |
| | INTERCEPTOR PER CITY OF WEST PALM BEACH UUTILITIES |
| | DEPARTMENT. |
| | D) SINKS AND DISHWASHERS SHALL DISCHARGE INDIRECTLY |
| | THROUGH AN AIR GAP OR AN AIR BREAK TO THE DRAINAGE |
| | SYSTEM PER FBC-PLUMBING SEC.802.1.6, 802.1.8, 802.2. |
| | 50) SHT. P-707 - DETAIL #5 - RIGID SSUPPORT SWAY |
| | BRACING SHALL BE PROVIDED AT CHANGES IN DIRECTION |
| | GREATER THAN 45 DEGREESFOR PIPE SSIZES 4 INHES AND |
| | LARGER. THE DETAIL REFERS TO PIPE 6 INCHES AND |
| | GREATER.ANCHORAGE SHALL BE PROVIDDED PER FBC-PLUMBING |
| | SECS.308.7 & 308.7.1. |
| | |
| | FUEL TANK/ FUEL PIPING |
| | |
| | 51) SUBMIT A COPY OF THE UL 142 CERTIFICATION FOR THE |
| | FUEL TANK PER NFPA 30 SEC. 2.3.9, 21.4.2. |
| | 52) INDICATE THE TYPE OF FUEL AND THE CLASS OF |
| | COMBUSTIBLE LIQUID ( CLASS II, CLASS IIA, CLASS III A |
| | OR CLASS III B) OF THE FUEL ON THE PLANS PER NFPA 330 |
| | SEC.4.3.2. |
| | 53) SUBMIT COPIES OF THE SAFETY DATA SHEETS FOR THE |
| | FUEL. |
| | 54) SUBMIT SPECIFICATIONS FOR THE FUEL TANK SHOWING |
| | COMPLIANCE WITH NFPA 30. |
| | 55) SUBMIT PIPING DETAILS/ RISER DIAGRAM FOR THE NORMAL |
| | VENTING AND EMERGENCY VENTING OF THE FUEL TANK. VENT |
| | PIPING SHALL COMPLY WITH NFPA 30 SEC.27.8. |
| | 56) THE FUEL TANK VENTS SHALL BE LOCATED 5 FEET FROM |
| | ANY BUILDING OPENINGS, A MINIMUM OF 12 FEET ABOVE THE |
| | ADJACENT GROUND LEVEL AND 15 FEET FROM POWERED |
| | VENTILATION AIR INTAKES PER NFPA 30 SEC. 27.8.1.1, |
| | 27.8.1.3. |
| | 57) SUBMIT A FUEL PIPING RISER DIAGRAM FOR THE SUPPLY & |
| | RETURN FUEL PIPING FOR THE 2,000 GALLLON FUEL TANK |
| | INCLUDING THE PIPING TO THE FUEL POLISHING SYSTEM AND |
| | ALSO FROM THE FUEL FILL PORT TO THE TANK. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 58) SUBMIT SPECIFICATIONS/ INFORMATION ON THE FUEL |
| | POLISHING SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 59) SUBMIT A LEGEND FOR THE LETTERS SHOWN ON THE 2,000 |
| | FUEL TANK ON SHT. P-242. |
| | 60) PROVIDE DETAILS ON PROVISIONS FOR THE PROMPT AND |
| | SAFE MIITIGATION AND DISPOSAL OF LEAKAGE OR SPILLS PER |
| | NFPA 30 SEC. 18.4.2. |
| | 61) TANK FILL PIPES THAT ENTER THE TOP OF A TANK SHALL |
| | TERMINATE WITHIN 6 INCHES OF THE BOTTOM OF THE TANK. |
| | NFPA 30 SEC. 21.4.4. |
| | 62) EACH CONNECTION TO AN ABOVEGROUND TANK THROUGH |
| | WHICH LIQUID CAN NORMALLY FLOW SHALL BE PROVIDED WITH |
| | AN INTERNAL OR AN EXTERNAL VALVE LOCATED AS CLOSE AS |
| | PRACTICAL TO THE SHELL OF THE TANK.NFPA 30 SEC. |
| | 22.13.1. REFER TO THE SUPPLY AND RETURN LINES TO THE |
| | GENERATOR. |
| | 63) SHT.P-242 - THE SUPPLY AND RETURN LINES TO THE |
| | GENERATOR APPEAR TO BE MISLABELED AS TO THE FLOW. |
| | CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |