Plan Review Notes
Plan Review Notes For Permit 20070795
Permit Number 20070795
Review Stop B
Sequence Number 2
Notes
Date Text
2020-09-16 12:57:08PLAN REVIEW COMMENTS
 REVISION TO PERMIT #18081528
 25 STORY, R-2 HIGH RISE
 TYPE IA CONSTRUCTION
 1ST REVIEW: FBC SIXTH EDITION (2017) ( I WAS LOCKED OUT
 OF THE FIRST REVIEW.)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A-001A THERE ARE NOTES STATING THAT ALL
 OPENINGS LEADING TO INTERIOR AREAS BELOW BASE FLOOD
 ELEVATION SHALL BE PROVIDED WITH FLOOD PANELS. THIS
 PROPERTY HAS A LOMR-F, CASE NUMBER 19-04-1248A, THAT
 REMOVES IT FROM THE SPECIAL FLOOD HAZARD AREA AND
 CHANGES IT TO AN X FLOOD ZONE. SEE NOTES UNDER THE NFIP
 REVIEW STOP FOR PERMIT NUMBER 18081528. THERE IS NO
 LONGER A BASE FLOOD ELEVATION FOR THIS PROPERTY.
  
 2) ON SHEET LS-1, PG 129, THERE ARE SOME THINGS MISSING
 FROM THE LIFE SAFETY PLAN. THE TRAVEL DISTANCE WAS NOT
 CHANGED TO REFLECT THE REVISION TO THE ACCESS CORRIDOR
 TO STAIR 1. THE THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING AND REQUIRED EXIT
 SEPARATION CALCULATION IS NOT SHOWN. THE EXIT
 SEPARATION DISTANCE NEEDS TO BE CORRECTED. SHOW THE
 DISTRIBUTION OF THE OCCUPANTS AND NUMBER OF OCCUPANTS
 USING EACH ONE THAT IS EQUAL TO THE TOTAL OCCUPANT LOAD
 FOR THIS STORY. CITY AMENDMENTS FBC 107.2.1 AND FBC
 CHAPTER 10.
  
 3) ON SHEET LS-2, PG130, SHOW THE DISPERSEMENT AND
 NUMBER OF THE OCCUPANTS TO EACH EXIT, SUCH THAT THE
 TOTAL EQUALS THE OCCUPANT LOAD OF THE STORY. FBC 1005.5
 DISTRIBUTION OF MINIMUM WIDTH AND REQUIRED CAPACITY
  
 4) ON SHEET LS-3, PG 131, THE LENGTH OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE BUILDING NEEDS TO BE
 ADJUSTED TO REFLECT THE REVISION TO THE STAIRS. FBC
 1007.1 THE PLAN SHOWS 170 OCCUPANTS USING STAIRS 1 AND
 2. THE NOTES SHOW THE MAXIMUM CAPACITY OF THESE STAIRS
 IS 160 OCCUPANTS. PLEASE CORRECT. SHOW THE DISPERSEMENT
 AND NUMBER OF THE OCCUPANTS TO EACH EXIT, SUCH THAT THE
 TOTAL EQUALS THE OCCUPANT LOAD OF THE STORY. FBC 1005.5
  
 5) ON SHEET LS-4, PG132, SHOW THE EXIT SEPARATION
 DISTANCE. FBC 1007.1 SHOW THE DISPERSEMENT AND NUMBER
 OF THE OCCUPANTS TO EACH EXIT, SUCH THAT THE TOTAL
 EQUALS THE OCCUPANT LOAD OF THE STORY. FBC 1005.5 THE
 TOTAL OCCUPANT CAPACITY WAS NOT PROVIDED.
  
 6) SHEET A-916, PG 282.3 IS A SHOWER PAN DETAIL AND NOT
 FLOOR TRANSITION DETAILS AS TITLED. FBC 107.2.1
  
 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  