| 2020-09-21 09:45:26 | 1) SHT.G-10 - 010.20180831 - PLUMBING FIXTURE SCHEDULE |
| | - TAG #F38 STATES VERTICAL GRAB BARS ARE TO BE |
| | INSTALLED IN THE 2ND AND 3RD LEVEL ADA WATER CLOSETS. |
| | THE GRAB BARS MUST BE INSTALLED IN THE HORIZONTAL |
| | POSITION PER ANSI A117.1-1986 SECS.4.16.4 & 4.17.6 |
| | WHICH COVERS THE COMMON AREA REQUIREMENTS. THERE IS NO |
| | EXCEPTION FOR GRAB BARS TO BE INSTALLED IN THE VERTICAL |
| | POSITION. |
| | 2) SHT. G-10 - 010.20180831 - PLUMBING FIXTURE SCHEDULE |
| | - TAG #F25 REFERS TO A KOHLER WALL-MOUNT BATHROOM SINK |
| | & FAUCET WITH CROSS HANDLES. THESE HANDLES DO NOT MEET |
| | THE INTENT OF ANSI A117.1-1986 SECS.4.19.5 & 4.25.4. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THIS ITEM. |
| | NOTE: BLADE HANDLES ARE AVAILABLLE FROM THE |
| | MANUFACTURER FOR THIS ITEM. |
| | 3) SHT. A-110 - THE SUBMITTED NARRATIVE STATES "ADDED |
| | ROOF DRAIN CALCS." BUT THERE ARE NO CALCULATIONS ON |
| | THIS SHEET. CLARIFY. COMPLY WITH FBC-PLUMBING |
| | SEC.1105.2, 1106. |
| | 4) SHT.A-220 - UNIT "A" - SHOW ON THE PLAN WHICH FAIR |
| | HOUSING BATHROOM DESIGN SPECIFICATION (A OR B) IS USED |
| | FOR THE MASTER BATH.SHOW THE REQUIRED CLEAR FLOOR SPACE |
| | ADJACENT TO THE SHOWER ON SHT.A-770. |
| | 5) SHT. A-220 - UNIT "A" - THE SHOWER DOOR SWING IN THE |
| | MASTER BATH DOES NOT CORRELATE WITH THE DOOR SWING ON |
| | SHT. A-770. - CLARIFY. |
| | 6) SHT. A222 - UNIT "C" - THE LOCATION OF THE SHOWER |
| | CONTROLS SHOWN IN THE FHA BATHROOM IN DETAIL # 1 DO NOT |
| | CORRELATE WITH THE LOCATION OF THE CONTROLS SHOWN IN |
| | THE SHOWER ON SHT. A-771, DETAIL # 17. CLARIFY. |
| | 7) SHT. A-223 - UNIT "D" - DETAIL #1 - THE LAYOUT OF |
| | THE PLUMBING FIXTURES IN BATHROOM #2 DOES NOT CORRELATE |
| | WITH THE FIXTURE LAYOUT IN DETAIL #17 ON SHT. A-771. |
| | CLARIFY. |
| | 8) SHT. A-224 - UNIT "E" - DETAIL #2 REFERS TO DETAIL |
| | #12 ON SHT. A-772 BUT SHT. A-772 HAS NOT BEEN INCLUDED |
| | IN THIS SUBMITTAL. CLARIFY. |
| | 9) SHT.A-225 - UNIT "F" - DETAIL #1 - THE LOCATION OF |
| | THE SHOWER CONTROLS IN THE FHA BATHROOM #2 DO NOT |
| | CORRELATE WITH THE LOCATION OF THE SHOWER CONTROLS ON |
| | SHT.A-771, DETAIL #17. ALSO, SHT. A-225 SHOWS A DOOR ON |
| | THE SHOWER AND SHT. A-771 DOES NOT AND THE DOOR SWING |
| | INTO THE BATHROOM IS REVERSED ON THE SAME DRAWINGS. |
| | 10) SHT. A-226A - UNIT "G" - DETAIL #1 - THE LAYOUT OF |
| | THE PLUMBING FIXTURES IN BATHROOM #2 DOES NOT CORRELATE |
| | WITH THE FIXTURE LAYOUT IN DETAIL #17 ON SHT. A-771. |
| | CLARIFY. |
| | 11) THE LOCATION OF THE SHOWER CONTROLS ON SHT. A-226A, |
| | DETAIL #1 DOES NOT CORRELATE WITH SHT. A-771, DETAIL |
| | #17. CLARIFY. |
| | 12) SHT. A-227A - DETAIL #1 - THE LOCATION OF THE |
| | SHOWER CONTROLS SHOWN IN THE FHA BATHROOM #3, DETAIL # |
| | 1 DO NOT CORRELATE WITH THE LOCATION OF THE CONTROLS |
| | SHOWN IN THE SHOWER ON SHT. A-771, DETAIL # 17 AND THE |
| | DOOR SWING INTO THE BATHROOM IS REVERSED ON THE SAME |
| | DRAWINGS. CLARIFY. |
| | 13) SHT. A-227A - THE FAIR HOUSING ACT DESIGN MANUAL |
| | PAGE 7.56 REQUIRES A 30 INCH X 48 INCH CLEAR FLOOR |
| | SPACE BE PROVIDED AT SHOWER STALLS, PARALLEL TO THE |
| | FIXTURE AND FLUSH WITH THE CONTROL WALL. SUBMIT |
| | JUSTIFICATION AS TO HOW THE CURRENT DESIGN MEETS THIS |
| | REQUIREMENT AND THE INTENT OF THE DESIGN MANUAL. AS |
| | CURRENTLY DESIGNED, THE LAYOUT DOES NOT APPEAR TO |
| | COMPLY WITH THE FAIR HOUSING ACT DESIGN MANUAL. |
| | 14) SHT. A-228A - DETAIL #1 - PROVIDE THE PLAN SHEET |
| | NUMBER AND DETAIL NUMBER FOR THE ENLARGED FLOOR PLAN |
| | FOR THE FHA BATHROOM #3. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 15) ) - SHT. A-230 - DETAIL #5 - SHOW THE HEIGHT OF THE |
| | KITCHENETTE COUNTER WITH THE SINK.COMPLY WITH THE FHA |
| | DEESIGN MANUAL. |
| | 16) SHT.A-241 - DETAIL #11 SHOWS A VERTICAL GRAB BAR. |
| | THE GRAB BARS MUST BE INSTALLED IN THE HORIZONTAL |
| | POSITION PER ANSI A117.1-1986 SECS.4.16.4 & 4.17.6 |
| | WHICH COVERS THE COMMON AREA REQUIREMENTS. THERE IS NO |
| | EXCEPTION FOR GRAB BARS TO BE INSTALLED IN THE VERTICAL |
| | POSITION. |
| | 17) SHT. A-243A - DETAIL #1- THE URINAL IN THE MEN'S |
| | SPA SHALL BE PROVIDED WITH WALLS OR PARTITIONS TO |
| | PROVIDE PRIVACY PER 2017 FBC SEC.1210.3.2. |
| | 18) SHT A-243A - MEN'S AND WOMEN'S ADA SHOWER - SHOWER |
| | STALL SIZE AND CLEAR FLOOR SPACE SHALL COMPLY WITH ANSI |
| | A117.1-1986 SECS. 4.21.1, 4.21.2, 4.21.4, 4.21.5, |
| | 4..21.6, 4.21.8. THE POSITION OF THE ENCLOSURE DOOR |
| | IMPEDES THE USE OF THE CONTROLS. AS DESIGNED, THESE |
| | SHOWERS DO NOT COMPLY WITH THE SIZE REQUIREMENTS AS |
| | STATED IN THE ANSI DOCUMENT. |
| | 19) SHT.A-243B - THE HEIGHT OF THE WATER CLOSETS SHALL |
| | BE 17-19 INCHES ABOVE THE FINISH FLOOOR TO THE TOP OF |
| | THE SEAT PER ANSI A117.11- 1986 SEC. 4.16.3. DETAILS #5 |
| | & #6 SHOW THE WATER CLOSETS 16 INCHES ABOVE THE FINISH |
| | FLOOR.CLARIFY. |
| | 20) SHT. A-245 - DETAILS #1 & #12 SHOW GRAB BARS IN THE |
| | VERTICAL POSITION. THE GRAB BARS MUST BE INSTALLED IN |
| | THE HORIZONTAL POSITION PER ANSI A117.1-1986 |
| | SECS.4.16.4 & 4.17.6 WHICH COVERS THE COMMON AREA |
| | REQUIREMENTS. THERE IS NO EXCEPTION FOR GRAB BARS TO BE |
| | INSTALLED IN THE VERTICAL POSITION. |
| | 21) SHT. A-245 - DETAILS #12 & #13 - SHOW THE CLEARANCE |
| | FOR THE LAVATORIES FROM THE FINISH FLOOR TO THE BOTTOM |
| | OF THE LAVATORY. LAVVATORIES SHALL BE MOUNTED WITH A |
| | CLEARANCE OF AT LEAST 29 INCHES FROM THE FLOOR TO THE |
| | BOTTOM OF THE APRON PER ANSI A117.1-1986 SEC. 4.19.2.1. |
| | 22) SHT. A-247 - DETAIL #8 APPEARS TO SHOW PAINT ON THE |
| | WALL AT THE WATER CLOSET. WALLS AND PARTITIONS WITHIN 2 |
| | FEET OF WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR PER FBC-BUILDING SEC. 1210.2.2. |
| | EPOXY PAINT DOES MEET THE REQUIREMENTS OF THIS CODE |
| | SECTION. |
| | 23) SHT. A-626 - DETAIL #1 - PROVIDE THE DIMENSIONS OF |
| | THE ALUMINUM TUBE SCUPPER DRAINS FOR THE BALCONY.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 24) SHT. A-770 - DETAIL #1 - SHOW THE REQUIRED 30 X 48 |
| | INCH CLEAR FLOOR SPACE IN THE TOILET ROOM THAT IS |
| | REQUIRED OUTSIDE THE SWING OF THE DOOR PER THE FAIR |
| | HOUSING ACT DESIGN MANUAL. |
| | 25) SHT. A-770 - DETAIL #1 - SHOW THE REQUIRED 30 X 48 |
| | INCH CLEAR FLOOR SPACE AT THE SHOWER, PARALLEL TO THE |
| | FIXTURE AND FLUSH WITH THE CONTROL WALL PER THE FHA |
| | DESIGN MANUAL. |
| | 26) SHT. A-771 - DETAIL #17 - THE FAIR HOUSING ACT |
| | DESIGN MANUAL PAGE 7.56 REQUIRES A 30 INCH X 48 INCH |
| | CLEAR FLOOR SPACE BE PROVIDED AT SHOWER STALLS, |
| | PARALLEL TO THE FIXTURE AND FLUSH WITH THE CONTROL |
| | WALL. SUBMIT JUSTIFICATION AS TO HOW THE CURRENT DESIGN |
| | MEETS THIS REQUIREMENT AND THE INTENT OF THE FAIR |
| | HOUSING ACT DESIGN MANUAL. AS CURRENTLY DESIGNED, THE |
| | LAYOUT DOES NOT APPEAR TO COMPLY WITH THE FAIR HOUSING |
| | ACT DESIGN MANUAL. |
| | 27) SHT. A-774 - DETAIL #7 - THE FAIR HOUSING ACT |
| | DESIGN MANUAL PAGE 7.56 REQUIRES A 30 INCH X 48 INCH |
| | CLEAR FLOOR SPACE BE PROVIDED AT SHOWER STALLS, |
| | PARALLEL TO THE FIXTURE AND FLUSH WITH THE CONTROL |
| | WALL. SUBMIT JUSTIFICATION AS TO HOW THE CURRENT DESIGN |
| | MEETS THIS REQUIREMENT AND THE INTENT OF THE DESIGN |
| | MANUAL. AS CURRENTLY DESIGNED, THE LAYOUT DOES NOT |
| | APPEAR TO COMPLY WITH THE FAIR HOUSING ACT DESIGN |
| | MANUAL. |
| | 28) SHT. A-790 - THE PLANS SHOW KITCHEN ELEVATION |
| | LETTER TAGS AND ALSO TYPE 1 & TYPE 2 ELEVATION TAGS. |
| | CLARIFY. |
| | 29) SHT. A-917A - DETAIL #9 - THERE IS NO ELEVATION |
| | DETAIL FOR ADA SINK "A". CLARIFY. |
| | 30) SHT. A-917A - DETAIL #17 - SHOW THE REQUIRED KNEE |
| | AND TOE CLEARANCES PER ANSI A117.1-1986 SEC.4.19.2.1. |
| | 31) SHT. P-001 - NOTES #22 & #24 REFER TO THE 2014 |
| | FLORIDA BUILDING CODES. THE 2017 FLORIDA BUILDING CODE |
| | APPLIES TO THIS PROJECT. REVISE THE NOTE. |
| | 32) SHT. P-001 - NOTE #26 REFERS TO THE 2010 FLORIDA |
| | BUILDING CODE-PLUMBING. REVISE THE NOTE TO REFER TO THE |
| | 2017 FBC-PLUMBING. |
| | 33) SHT. P-001 - NOTE #50 - CHANGE THE REFERENCE FROM |
| | FLORIDA PLUMBING CODE 2014 TO 2017 FLORIDA PLUMBING |
| | CODE. |
| | 34) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE |
| | SAND/OIL INTERCEPTOR. THE INTERCCEPTOR SHALL COMPLY |
| | WITH FBC-PLUMBING SEC.1003.4.2, 1003..4.2.1. |
| | 35) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR HE HAIR |
| | INTERCEPTOR. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 36) THE STRUCTURAL DRAWINGS FOR THE BASEMENT LEVEL SHOW |
| | ADDED SUMP PITS. IS THERE PIPING AND EJECTOR PUMPS |
| | BEING INSTALLED IN THESE PITS? IF SO, SHOW THE PUMPS |
| | AND PIPING ON SHT.P-100A & P-100B AND PROVIDE A TYPICAL |
| | SUMP DETAIL WITH THE PUMP AND DISCHARGE PIPING & |
| | VALVES, ETC. AND ALSO SHOW THIS ON THE APPLICABLE RISER |
| | DIAGRAM. WPB AMEND. TO FBC SE. 107.2.1. |
| | 37) SHT. P-101A - PROVIDE MATCH LINES ON THE PLANS.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 38) SHT. P-101A - PROVIDE THE CONTINUATION POINTS FOR |
| | THE 1 1/2 INCH GAS LINE BETWEEN COLUMN LINES GE-GF, THE |
| | STORM DRAIN LINES AT COLUMN LINES GA,GJ,GL,AND GM AND |
| | ALL OTHER LINES SHOWN ON THIS PLAN. IDENTIFY THE GAS |
| | LINE TO TE POOL HEATER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 39) SHT. P-101A - THE PLAN SHOWS A 4 INCH HUB DRAIN FOR |
| | POOL MAINTENANCE CONNECTED TO THE STORM SYSTEM (AT GRID |
| | LINES GL/GM & G10) AND ALSO A 6 INCH HUB DRAIN FOR POOL |
| | BACKWASH TO THE SANITARY SYSTEM AT GRID LINES ( G10 & |
| | GJ). POOL WATER IS NOT PERMITTED TO DISCHARGE TO THE |
| | CITY'S STORM SYSTEM PER CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES CHAPTER 90, ARTICLE V, SEC.90-203 (A). POOL |
| | WATER SHALL NOT DISCHARGE TO THE CITY'S SANITARY SYSTEM |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER |
| | 90, ARTICLE III, SEC. 90-126 (B)(5) UNLESS SPECIFICALLY |
| | AUTHORIZED BY THE CITY IN WRITING. PLEASE CONTACT MANNY |
| | GONZALEZ IN THE CITY'S ENGINEERING DEPARTMENT AT |
| | 561-494-1085 OR AT [email protected] FOR FURTHER |
| | INFORMMATION. |
| | 40) SHT. P-101A - PROVIDE MATCH LINES ON THE PLANS TO |
| | SHOW THE CONTINUATION OF THE PIPING SYSTEMS. IDENTIFY |
| | THE PIPING THAT IS LOCATED IN THE OFFICE/PACKAGING AREA |
| | AND THE PACKAGING BOH AREA.WPB AMEND. TO FBC |
| | SEC.107.2.1. |
| | 41) SHT. P-101B - A LEAD-FREE BACKFLOW PREVENTION |
| | DEVICE ( RPZ ) SHALL BE INSTALLED ON THE TRIPLEX WATER |
| | FILTRATION SYSTEM AND THE WATER SOFTENING SYSTEM PER |
| | FBC-PLUMBING SEC.608.3. |
| | 42) SHT. P-101B - PROVIDE MATCH LINES ON THE PLAN AND |
| | IDENTIFY THE USE OF THE PIPING SYSTEMS ON THE PLANS, |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 43) SHT.P-102B - PROVIDE MATCH LINES ON THE PLAN AND |
| | IDENTIFY THE USE OF THE PIPING SYSTEMS ON THE PLANS, |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 44) SHT. P-220 - SANITARY PIPING ISOMETRICS - THERE ARE |
| | TWO WASHING MACHINES DISCHARGING INTO A TWO-INCH WASTE |
| | STACK AND HORIZONTAL DRAIN.THE MINIMUM SIZE WASTE STACK |
| | AND HORIZONTAL DRAIN SHALL BE 3- INCH PER FBC-PLUMBING |
| | SEC. 406.2. |
| | 45) THE WATER SHUTOFF VALVES FOR THE WASHING MACHINES |
| | SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING |
| | SEC.606.3. |
| | 46) SHT. P-221 - SANITARY PIPING ISOMETRICS - THERE ARE |
| | TWO WASHING MACHINES DISCHARGING INTO A TWO- INCH WASTE |
| | STACK AND HORIZONTAL DRAIN.THE MINIMUM SIZE WASTE STACK |
| | AND HORIZONTAL DRAIN SHALL BE 3- INCH PER FBC-PLUMBING |
| | SEC. 406.2. |
| | 47) SHTS. P-222,P-223 - SANITARY PIPING ISOMETRICS - |
| | THERE ARE TWO WASHING MACHINES DISCHARGING INTO A TWO- |
| | INCH WASTE STACK AND HORIIZONTAL DRAIN.THE MINIMUM SIZE |
| | WASTE STACK AND HORIZONTAL DRAIN SHALL BE 3- INCH PER |
| | FBC-PLUMBING SEC. 406.2. |
| | 48) SHT. P-224 - THERE ARE TWO WASHING MACHINES SHOWN |
| | ON THE FLOOR PLAN BUT ONLY ONE SHOWN ON THE SANITARY |
| | AND WATER RISERS. CLARIFY. |
| | 49) SHT. P-224 - THE WASHING MACHINE STANDPIPE SHALL |
| | DISCHARGE INTO A MINIMUM 3-INCH OR LARGER DIAMETER |
| | FIXTURE BRANCH OR STACK. FBC-PLUMBING SEC.406.2. |
| | 50) SHT. P-241 - SANITARY PIPING ISOMETRIC DINING AREA |
| | - THE VENT PIPING FOR THE GREASE TRAP APPEARS |
| | INCOMPLETE. ALSO, SUBMIT SIZING CALCULATIONS FOR THIS |
| | UNIT. 2017 FBC- PLUMBING SEC 1003.2. |
| | 51) SHT. P- 503A - STORM RISER #ST 8 - THERE IS A |
| | 4-INCH HORIZONTAL DRAIN THAT DOES NOT CONNECT TO |
| | ANYTHING. CLARIFY. |
| | 52) SIZE THE VENT STACKS,SOIL STACKS AND WASTE STACKS |
| | ON THE SANITARY PIPING ISOMETRICS ON THE ENLARGED UNIT |
| | PLANS. WPB AMEND. TO FBC SEC.107.2.1. |
| | 53) SHT P-506 - STORM DRAINAGE PIPING ISOMETRIC - ADD |
| | RISER TAG NUMBERS TO THE PIPING ISOMETRIC. WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 54) SHT. P-506 - SUPPLY THE DRAWING NUMBER OF THE PLANS |
| | ON WHICH THE PLUMBING RISERS CAN BE FOUND. |
| | 55) SHT. P-506 - THERE ARE ADDITIONAL RISERS ( 4" W UP, |
| | 3" W UP, 4" S UP ) SHOWN ON SHT. P-100B THAT ARE NOT |
| | SHOWN ON THE SANITARY PIPING ISOMETRIC ON SHT. P-506. |
| | CLARIFY. |
| | 56) SHT. P-708 - SHOWS THE FUEL TANK AS 2,000 GALLONS |
| | AND SHT. P-242, DETAIL #2 SHOWS THE TANK AS 4,000 |
| | GALLONS. THE SPECIFICATIONS ON SHT. E-407 ALSO CALL OUT |
| | A 2,000 GALLON FUEL TANK.CLARIFY. |
| | 57) SHT. P-503A - THERE IS A SMALL STORM RISER DIAGRAM |
| | AT THE BOTTOM OF THE PAGE WITH A 4 INCH PD DRAIN. THERE |
| | IS TEXT REFERRING TO 2- SIX INCH STORM DRAINS BUT NO |
| | PIPING IS SHOWN. CLARIFY. |
| | 58) SHT, P-506 - SHOW THE HAIR INTERCEPTOR ON THE |
| | SANITARY PIPING ISOMETRIC THAT IS SHOWN ON THE PLAN |
| | VIES ON SHT. P-100B. |
| | 59) SHT. P-503A - SUBMIT A REVISED STORM RISER DIAGRAM |
| | FOR THE ADDED TERRACE DRAINS FOR THE AFFECTED UNITS. |
| | RISER ST/9 ON SHT. P-503A DOES NOT SHOW ALL THE DRAINS. |
| | 60) THE ISLAND VENT FOR THE KITCHEN SINK SHOWN ON THE |
| | ELARGED PLUMBING FLOOR PLANS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH FBC-PLUMBING SECS.916.1-916.3.CLEANOUTS |
| | SHALL BE PROVIDED IN THE ISLAND FIXTURE VENT TO PERMIT |
| | RODDING OF ALL VENT PIPING LOCATED BELOW THE FLOOD |
| | LEVEL RIM OF THE FIXTURES. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | REVIEW IS INCOMPLETE |