| 2020-08-15 12:04:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 20070795 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-001: PLEASE USE THE CURRENT EDITION 2017 FBC |
| | M. THE MENTIONED CODE SECTION FOR NOTE 23 IS NOT IN |
| | THIS EDITION. FBC M 504.6 |
| | |
| | 2) SHEET M-001: NOTE 22- DRYER EXHAUST DUCT POWER |
| | VENTILATORS SHALL BE LISTED AND LABELED TO UL 705 AND |
| | INSTALLED IN ACCORDANCE TO MANUFACTURER?S INSTRUCTIONS. |
| | FBC M 504.6 |
| | |
| | 3) SHEET M-001: NOT 22- DRYER EXHAUST DUCT POWER |
| | VENTILATOR LENGTH SHALL BE DETERMINED BY THE |
| | MANUFACTURER?S INSTALLATION INSTRUCTIONS. PLEASE |
| | PROVIDE MANUFACTURER AND THEIR INSTALLATION |
| | INSTRUCTIONS. FBC M 504.8.4.3 |
| | |
| | 4) SHEET M-101A: NOTE (8) DOES NOT APPEAR TO BELONG AT |
| | THE 2 SWINGING DOORS. PLEASE VERIFY AND EXPLAIN. FBC FS |
| | 107.2.1 |
| | |
| | 5) SHEET M-102A: THE WALL AT THE TRASH ROOM APPEARS TO |
| | BE RATED ON THE A SHEET. PLEASE SHOW THE REQUIRED FD AT |
| | THE DUCT PENETRATION OF THIS WALL. FBC M 607.5 |
| | |
| | 6) SHEET M-102B: THE WALL AT THE TRASH ROOM APPEARS TO |
| | BE RATED ON THE A SHEET. PLEASE SHOW THE REQUIRED FD AT |
| | THE DUCT PENETRATION OF THIS WALL. FBC M 607.5 |
| | |
| | 7) SHEET M-103: PLEASE PROVIDE DAMPERS IN ALL DUCTS |
| | THAT PENETRATE RATED WALLS. ( RED LINES ON SHEET |
| | INDICATE AREAS THAT APPEAR TO NEED FD?S. FBC M 607.5 |
| | |
| | 8) SHEET M-110: SEF-1 DUCT SIZE ON ROOF HAS CHANGED |
| | FROM PREVIOUSLY APPROVED PLANS. PLEASE SHOW THIS |
| | CLOUDED AND INDICATE WHY IT HAS CHANGED. FBC FS 107.2.1 |
| | |
| | 9) SHEET M-110: ROOF ACCESS LADDER HAS BEEN REMOVED |
| | FROM THE PLANS ON THIS REVISED SHEET. PLEASE SHOW THE |
| | LADDER THAT WAS PREVIOUSLY APPROVED. FBC FS 107.2.1 |
| | |
| | 10) SHEETS M-220, 221, 223, 224: PROVIDE SPEC SHEETS |
| | FOR THE NEW HOODS. PROVIDE SPEC SHEETS FOR THE RANGES. |
| | PLEASE EXPLAIN WHY THE REDUCTION FITTING TO REDUCE THE |
| | EXHAUST FLOW OF THE HOODS? FBC FS 107.2.1 |
| | |
| | 11) SHEETS M-227, 228: PLEASE EXPLAIN WHY THE SINGLE |
| | XVENT CHANGED TO A DOUBLE HORIZONTAL EXHAUST BOX. THERE |
| | APPEARS TO BE ONLY 1 DUCT CONNECTED TO IT. FBC FS |
| | 107.2.1 |
| | |
| | 12) SHEET M-502: PLEASE PROVIDE AN OPERATION MATRIX OF |
| | THE NEW ELEVATOR PRESSURIZATION. EXPLAIN FANS PLACEMENT |
| | AND THE OMISSION OF THE ROOF DAMPER. FBC FS 107.2.1 |
| | |
| | 13) SHEET M-502: PLEASE PROVIDE AN AIR BALANCE REPORT |
| | FOR THE NEW ELEVATOR PRESSURIZATION LAYOUT. FBC FS |
| | 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |