Plan Review Notes
Plan Review Notes For Permit 20070795
Permit Number 20070795
Review Stop M
Sequence Number 1
Notes
Date Text
2020-08-15 12:04:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20070795
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-001: PLEASE USE THE CURRENT EDITION 2017 FBC
 M. THE MENTIONED CODE SECTION FOR NOTE 23 IS NOT IN
 THIS EDITION. FBC M 504.6
  
 2) SHEET M-001: NOTE 22- DRYER EXHAUST DUCT POWER
 VENTILATORS SHALL BE LISTED AND LABELED TO UL 705 AND
 INSTALLED IN ACCORDANCE TO MANUFACTURER?S INSTRUCTIONS.
 FBC M 504.6
  
 3) SHEET M-001: NOT 22- DRYER EXHAUST DUCT POWER
 VENTILATOR LENGTH SHALL BE DETERMINED BY THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. PLEASE
 PROVIDE MANUFACTURER AND THEIR INSTALLATION
 INSTRUCTIONS. FBC M 504.8.4.3
  
 4) SHEET M-101A: NOTE (8) DOES NOT APPEAR TO BELONG AT
 THE 2 SWINGING DOORS. PLEASE VERIFY AND EXPLAIN. FBC FS
 107.2.1
  
 5) SHEET M-102A: THE WALL AT THE TRASH ROOM APPEARS TO
 BE RATED ON THE A SHEET. PLEASE SHOW THE REQUIRED FD AT
 THE DUCT PENETRATION OF THIS WALL. FBC M 607.5
  
 6) SHEET M-102B: THE WALL AT THE TRASH ROOM APPEARS TO
 BE RATED ON THE A SHEET. PLEASE SHOW THE REQUIRED FD AT
 THE DUCT PENETRATION OF THIS WALL. FBC M 607.5
  
 7) SHEET M-103: PLEASE PROVIDE DAMPERS IN ALL DUCTS
 THAT PENETRATE RATED WALLS. ( RED LINES ON SHEET
 INDICATE AREAS THAT APPEAR TO NEED FD?S. FBC M 607.5
  
 8) SHEET M-110: SEF-1 DUCT SIZE ON ROOF HAS CHANGED
 FROM PREVIOUSLY APPROVED PLANS. PLEASE SHOW THIS
 CLOUDED AND INDICATE WHY IT HAS CHANGED. FBC FS 107.2.1
  
 9) SHEET M-110: ROOF ACCESS LADDER HAS BEEN REMOVED
 FROM THE PLANS ON THIS REVISED SHEET. PLEASE SHOW THE
 LADDER THAT WAS PREVIOUSLY APPROVED. FBC FS 107.2.1
  
 10) SHEETS M-220, 221, 223, 224: PROVIDE SPEC SHEETS
 FOR THE NEW HOODS. PROVIDE SPEC SHEETS FOR THE RANGES.
 PLEASE EXPLAIN WHY THE REDUCTION FITTING TO REDUCE THE
 EXHAUST FLOW OF THE HOODS? FBC FS 107.2.1
  
 11) SHEETS M-227, 228: PLEASE EXPLAIN WHY THE SINGLE
 XVENT CHANGED TO A DOUBLE HORIZONTAL EXHAUST BOX. THERE
 APPEARS TO BE ONLY 1 DUCT CONNECTED TO IT. FBC FS
 107.2.1
  
 12) SHEET M-502: PLEASE PROVIDE AN OPERATION MATRIX OF
 THE NEW ELEVATOR PRESSURIZATION. EXPLAIN FANS PLACEMENT
 AND THE OMISSION OF THE ROOF DAMPER. FBC FS 107.2.1
  
 13) SHEET M-502: PLEASE PROVIDE AN AIR BALANCE REPORT
 FOR THE NEW ELEVATOR PRESSURIZATION LAYOUT. FBC FS
 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  