| Plan Review Notes For Permit 20070795 |
| Permit Number |
20070795 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-03 10:19:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-701 GENERATOR ROOM ENLARGERMENT | | | | | | THE FRAME OF THE GENERATOR AND THE GDP NEEDS PROPER | | | WORKING CLEARANCES OF 42" PER TABLE 110.26(A)(1) | | | CONDITION 2, 151 -- 600 VOLTS. | | | | | | PLEASE VERIFY, I WAS NOT ABLE TO USE MEASURING TOOL IN | | | PLAN REVIEW. |
|