| 2020-09-15 11:19:25 | PLAN REVIEW COMMENTS |
| | REVISION TO PERMIT #18081528 |
| | 25 STORY, R-2 HIGH RISE |
| | TYPE IA CONSTRUCTION |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) ****************** |
| | ****************************************************RE |
| | VIEW IN PROGRESS - NOT COMPLETE AT THIS |
| | TIME************ |
| | ****************************************** |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ON SHEET A-001A THERE ARE NOTES STATING THAT ALL |
| | OPENINGS LEADING TO INTERIOR AREAS BELOW BASE FLOOD |
| | ELEVATION SHALL BE PROVIDED WITH FLOOD PANELS. THIS |
| | PROPERTY HAS A LOMR-F, CASE NUMBER 19-04-1248A, THAT |
| | REMOVES IT FROM THE SPECIAL FLOOD HAZARD AREA AND |
| | CHANGES IT TO AN X FLOOD ZONE. SEE NOTES UNDER THE NFIP |
| | REVIEW STOP FOR PERMIT NUMBER 18081528. THERE IS NO |
| | LONGER A BASE FLOOD ELEVATION FOR THIS PROPERTY. |
| | |
| | 2) ON SHEET LS-1, PG 129, THERE ARE SOME THINGS MISSING |
| | FROM THE LIFE SAFETY PLAN. THE TRAVEL DISTANCE WAS NOT |
| | CHANGED TO REFLECT THE REVISION TO THE ACCESS CORRIDOR |
| | TO STAIR 1. THE THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE BUILDING AND REQUIRED EXIT |
| | SEPARATION CALCULATION IS NOT SHOWN. THE EXIT |
| | SEPARATION DISTANCE NEEDS TO BE CORRECTED. SHOW THE |
| | DISTRIBUTION OF THE OCCUPANTS AND NUMBER OF OCCUPANTS |
| | USING EACH ONE THAT IS EQUAL TO THE TOTAL OCCUPANT LOAD |
| | FOR THIS STORY. CITY AMENDMENTS FBC 107.2.1 AND FBC |
| | CHAPTER 10. |
| | |
| | 3) ON SHEET LS-2, PG130, SHOW THE DISPERSEMENT AND |
| | NUMBER OF THE OCCUPANTS TO EACH EXIT, SUCH THAT THE |
| | TOTAL EQUALS THE OCCUPANT LOAD OF THE STORY. FBC 1005.5 |
| | DISTRIBUTION OF MINIMUM WIDTH AND REQUIRED CAPACITY |
| | |
| | 4) ON SHEET LS-3, PG 131, THE LENGTH OF THE MAXIMUM |
| | OVERALL DIAGONAL DIMENSION OF THE BUILDING NEEDS TO BE |
| | ADJUSTED TO REFLECT THE REVISION TO THE STAIRS. FBC |
| | 1007.1 THE PLAN SHOWS 170 OCCUPANTS USING STAIRS 1 AND |
| | 2. THE NOTES SHOW THE MAXIMUM CAPACITY OF THESE STAIRS |
| | IS 160 OCCUPANTS. PLEASE CORRECT. SHOW THE DISPERSEMENT |
| | AND NUMBER OF THE OCCUPANTS TO EACH EXIT, SUCH THAT THE |
| | TOTAL EQUALS THE OCCUPANT LOAD OF THE STORY. FBC 1005.5 |
| | |
| | 5) ON SHEET LS-4, PG132, SHOW THE EXIT SEPARATION |
| | DISTANCE. FBC 1007.1 SHOW THE DISPERSEMENT AND NUMBER |
| | OF THE OCCUPANTS TO EACH EXIT, SUCH THAT THE TOTAL |
| | EQUALS THE OCCUPANT LOAD OF THE STORY. FBC 1005.5 THE |
| | TOTAL OCCUPANT CAPACITY WAS NOT PROVIDED. |
| | |
| | 6) |
| | |