2020-07-22 14:21:08RESIDENTIAL (R3) REROOF, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL12328-R8 SUBMITTED CAN NOT BE USED FOR THE PROPOSED
 INSTALLATION. THE PROPOSED ROOF TILE INSTALLATION IS
 USING TILE ADHESIVE. ACCORDING TO THE LAST NOTE UNDER
 APPLICATION METHOD ON PAGE 2 OF 4 OF PRODUCT APPROVAL
 SUBMITTED "ALL ROOF COVERINGS SHALL BE MECHANICALLY
 FASTENED THROUGH THE UNDERLAYMENT TO THE ROOF DECK".
 THEREFORE, NEED TO PROVIDE UNDERLAYMENT PRODUCT
 APPROVAL THAT IS DESIGNED FOR ROOF TILE ADHESIVE
 APPLICATIONS.
 FAC 61G20-3.001.
  
 2- ROOF TILE FL7473-R8 AND ROOF TILE ADHESIVE FL6332-R8
 SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE TO BE USED
 AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 3- SPECIFY ROOF PITCH, BUILDING MEAN HEIGHT AS REQUIRED
 BY CITY POLICY FOR ALL ROOFING PERMITS AND SEC.
 107.02.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  