| 2020-07-29 15:18:49 | 07/29/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FIREPLACE PER THE 2017 FBC FG SEC. 410.1. |
| | 2. THE RANGE SPECS DID NOT LOAD CORRECTLY ON PROJECT |
| | DOCS, PLEASE RELOAD, I CANNOT SEE IT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | 3. ON ISOMETRIC BTU'S LIST DOES NOT MATCH AMOUNT OF |
| | BTU?S, YOU DID NOT MULTIPLY THE TIKI TORCHES OR |
| | LANTERN, IE. YOU HAVE FIVE TIKI AT 22 BTU?S TIME 5 |
| | SHOULD EQUAL 110, YOU PUT ONLY 22 BTU?S, YOUR TOTAL |
| | SHOULD BE 886 BTU?S AND YOU HAVE 791 TOTAL BTU?S, |
| | PLEASE CORRECT ON BOTH SHEET OF ISO PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |