| 2021-02-18 17:01:04 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20070750 |
| | ADD: 515 CLEMATIS ST. |
| | CONT: NELSON CONSTRUCTION GC, INC. |
| | TEL: 305-331-1400 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. FEB. 18TH/2021 |
| | ACTION: DENIED |
| | |
| | 1) NOTE ONLY. THE VALUE OF THE PROJECT WITH DESIGN |
| | PROFESSIONAL FEES IS $194,982.00 AND LABOR AND |
| | MATERIALS. |
| | . |
| | 2) SHEET A-1,SITE PLAN, DEMO & LIFE SAFETY LEGEND. |
| | 2A) COMPLIED. |
| | |
| | 2B) COMPLIED. THIS BUILDING DOES QUALIFY AS A |
| | HISTORICAL BUILDING. HISTORIC PRESERVATION HAS ALREADY |
| | C COMMENTED THAT THE EXTERIOR OF THE BUILDING IS TO |
| | STAY BLOCK NO STUCCO. A NON-GLOSSY CONCRETE SEALER TO |
| | BE APPLIED ON THE ENTIRE FACE OF WALLS. 2017 FBC-B |
| | SECTION 1403.2 WEATHER PROTECTION. |
| | |
| | 2C-F) COMPLIED. |
| | |
| | 2G)SEMI-COMPLIED. THE 147 SQ. FEET OF OPENING OR 24% |
| | ALLOWABLE OPENINGS IS TAKING EITHER THE ALLOWABLE |
| | OPENINGS FOR 1 HOUR FIRE RATED WINDOWS OR FIRE |
| | SPRINKLERED BUILDING. TABLE 708.5 OF THE 2017 FBC-B FOR |
| | NON-SPRINKLERED BUILDINGS 10-15 FEET, ONLY ALLOWS 15 % |
| | UNPROTECTED OPENINGS. FOR EITHER PROTECTED OPENINGS OR |
| | THE BUILDING FIRE SPRINKLERED THE TABLE WOULD ALLOW 45% |
| | OPENINGS. THE NORTH ELEVATION ON SHEET A-3 NOR THE |
| | WINDOW SCHEDULE A-4 WINDOW MARK 3 INDICATE A FIRE RATED |
| | WINDOW IN COMPLIANCE WITH TALE 708.5 & SECTION 716.2 |
| | FIRE RESISTANCE RATED GLAZING. |
| | |
| | |
| | 2ND ROUND OF COMMENTS. PLEASE NOTE THE 701 SQUARE FEET |
| | TAKEN FOR THE NORTH WALL INCLUDES THE PARAPET. THE |
| | HEIGHT OF THE BUILDING IS TO BE TAKEN FROM FLOOR FINISH |
| | TO FLOOR FINISH OF THE NEXT STORY. FOR A SINGLE STORY |
| | BUILDING A STORY IS TO BE MEASURED FROM THE TOP OF THE |
| | FLOOR FINISH TO THE TOP OF THE CEILING JOIST OR WHERE |
| | THERE IS NOT A CEILING, TO THE TOP OF THE ROOF RAFTERS. |
| | SEE DEFINITION OF STORY CHAPTER 2OF THE 2017 FBC-B. |
| | 15.0 FT. X 40.5 FT.= 607.5 607.5/147= 0.24 % OPENINGS. |
| | TABLE 708.5 OF THE 2017 FBC-B FOR NON-SPRINKLERED |
| | BUILDINGS ONLY ALLOWS 15 % UNPROTECTED OPENINGS. FOR |
| | EITHER PROTECTED OPENINGS OR THE BUILDING FIRE |
| | SPRINKLERED THE TABLE WOULD ALLOW 45% OPENINGS. |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. SINCE THE WALL IS BEING FILED |
| | IN THE YES YOU ARE MAKING IT BETTER BUT IT IS NOT CODE |
| | COMPLIANT. TABLE 708.5 OF THE 2017 FBC-B FOR |
| | NON-SPRINKLERED BUILDINGS ONLY ALLOWS 15 % UNPROTECTED |
| | OPENINGS. FOR EITHER PROTECTED OPENINGS OR THE BUILDING |
| | FIRE SPRINKLERED THE TABLE WOULD ALLOW 45% OPENINGS. |
| | 1ST ROUND OF COMMENTS. NORTH LINE WALL, PLEASE PROVIDE |
| | AT WHAT PERCENTAGE OF WALL OPENINGS IS PROPOSED & IN |
| | CONFORMANCE WITH TABLE 705.8. UNPROTECTED OPENINGS. |
| | |
| | 2H-2I) COMPLIED. |
| | |
| | NEW COMMENTS: NEW SITE PLAN |
| | . |
| | 2J) ON THE NORTH SIDE OF THE BUILDING THERE IS A NEW |
| | RAMP AND LANDING SYSTEM. THE UPPER RAMP DOES REQUIRE A |
| | 90-DEGREE CHANGE IN DIRECTION WHICH REQUIRES THE RAMP |
| | TO BE A MINIMUM OF 60 INCHES BY 60 INCHES IN COMPLIANCE |
| | WITH 2017 ACCESSIBILITY CODE SECTION 405.7.4 AND THE |
| | 2017 FBC-BUILDING CODE SECTION 1012.6.4. |
| | |
| | 2K) THE SITE PLAN SHOWS A DOOR IN THE UPPER LANDING BUT |
| | THERE IS NO MEASUREMENT FROM THE EDGE OF THE DOOR TO |
| | WHERE THE TOP LANDING MEETS AND THE RAMP SLOPE BEGINS. |
| | PLEASE SHOW COMPLIANCE WITH 405.7.4 OF THE |
| | ACCESSIBILITY CODE AND SECTION 1012.6.5 OF THE 2017 |
| | FBC-B. |
| | |
| | 2L) THE SITE PLAN INDICATES A SLOPE OF 1:20 AND A RAMP |
| | LENGTH OF 10 FEET. THIS GIVES A HEIGHT OF 6 INCHES IN |
| | RISE. RAMPS WITH A RISE OF 6 INCHES OR LESS DO NOT |
| | REQUIRE A HANDRAIL BUT THEY DO NEED TO SHOW EDGE |
| | PROTECTION IN COMPLIANCE WITH 405.9 OF THE 2017 |
| | ACCESSIBILITY CODE AND SECTION 1012.10 OF THE 2017 |
| | FBC-B. |
| | |
| | 3)COMPLIED. ROOF PRESSURES. |
| | |
| | 4) BUILDING PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 5A) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5B BUILDING PROVISO: ) DELEGATED ENGINEERING. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 5C) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6) BUILING PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) COMPLIED. ROOFING SCUPPERS/ OVERFLOOWS NOT PART OF |
| | THIS PROJECT, ROOFING COMPLETED UNDER SEPARATE PERMIT. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |