| 2020-12-15 16:22:18 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20070750 |
| | ADD: 515 CLEMATIS ST. |
| | CONT: NELSON CONSTRUCTION GC, INC. |
| | TEL: 305-331-1400 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 01/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE VALUE OF THE PROJECT WITH DESIGN PROFESSIONAL |
| | FEES IS $194,982.00 AND LABOR AND MATERIALS. |
| | . |
| | 2) SHEET A-1,SITE PLAN, DEMO & LIFE SAFETY LEGEND. |
| | 2A) COMPLIED. |
| | |
| | 2B) COMPLIED. THIS BUILDING DOES QUALIFY AS A |
| | HISTORICAL BUILDING. HISTORIC PRESERVATION HAS ALREADY |
| | C COMMENTED THAT THE EXTERIOR OF THE BUILDING IS TO |
| | STAY BLOCK NO STUCCO. A NON-GLOSSY CONCRETE SEALER TO |
| | BE APPLIED ON THE ENTIRE FACE OF WALLS. 2017 FBC-B |
| | SECTION 1403.2 WEATHER PROTECTION. |
| | |
| | 2C) COMPLIED. HISTORIC BUILDING SEE COMMENT 2B. |
| | |
| | 2D) COMPLIED, OCCUPANT LOAD, 24 |
| | |
| | 2E) SEMI-COMPLIED. SHEET A-1 UNDER THE HEADING LIFE |
| | SAFETY LEGEND # 9 LIST THE CONSTRUCTION TYPE AS III-A. |
| | BOTH SHEETS A-5 AND S-2 HAVE THE SAME DETAIL OF A |
| | COLUMN TO ROOF FRAMING DETAIL. NOTES 17 AND 18 BOTH |
| | REFER TO THE FRAMING MEMBERS AS SOUTHERN YELLOW PINE. |
| | PLEASE REVIEW TABLE 601 OF THE 2017 FBC-B. FOR |
| | CONSTRUCTION TYPE III-A CONSTRUCTION REQUIRES THE ROOF |
| | CONSTRUCTION AND ALL ASSOCIATED SECONDARY MEMBERS AND |
| | DECKING TO BE 1 HOUR PROTECTED SINCE THE TOTAL FRAMING |
| | MEMBERS ARE LOWER THAN 20 FEET. PLEASE NOTE THE ROOF |
| | SHEATHING IS NOT DECLARED IN NOTE 17, ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | RESPONSE INDICATES ALL EXTERIOR WALLS ARE CONCRETE |
| | BLOCK / MASONRY WALLS WHICH CARRY A 2 HOUR RATING. |
| | PLEASE NOTE THE RINKER COMMON BLOCK ONLY CARRIED A 1 |
| | HOUR 45 MINUTE RATING WITH THE ? INCH STUCCO IT MADE |
| | THE 2 HOUR RATING. A BLOCK WOULD HAVE TO BE ANALYZED BY |
| | A LAB TO DETERMINE THE MINIMUM EQUIVALENT THICKNESS OF |
| | THE BEARING CONCRETE MASONRY BLOCK AND TYPE OF |
| | AGGREGATE, SEE TABLE 722.3.2 OF THE 2017 FBC-B. |
| | 1ST REVIEW COMMENT. NOTE # 9 INDICATES THE BUILDING |
| | CONSTRUCTION TYPE AS III. PLEASE PROVIDE IF THE MINIMUM |
| | BUILDING TYPE IS EITHER III-A OR III-B. TABLES 504.3, |
| | TABLE 504.4, TABLE 506.2, TABLE 601 & TABLE 602 OF THE |
| | 2017 FBC-B. TABLE 602, 0-5 FEET REQUIRES A 1 HOUR RATED |
| | WALL FOR BUSINESS OCCUPANCY. |
| | |
| | 2F) 2ND REQUEST. THE RESPONSE INDICATES THE CITY HAS AN |
| | AGREEMENT WITH THE OWNER TO ALLOW AN ACCESS EASEMENT TO |
| | ALLOW THE DOOR ON THE EAST SIDE OF THE BUILDING. |
| | WITHOUT DOCUMENTATION OF THIS DOCUMENT THIS COMMENT |
| | STILL REMAINS. THERE HAS TO BE BACK UP DOCUMENTATION |
| | SHOWING PROOF OF THIS AGREEMENT. |
| | 1ST ROUND OF COMMENTS. EAST PROPERTY LINE NOTE NUMBER |
| | 12 INDICATES THE CUTTING IN THE WALL A NEW EXTERIOR |
| | DOORWAY. SHEET A-2 ON THE FLOOR PLAN EAST WALL THE NEW |
| | OUTSWING DOOR IS LABELED E. PLEASE NOTE THAT DOORS & |
| | WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT |
| | OF WAY. 3202.2 OF THE 2017 FBC-B ALSO SEE TABLE 705.8 |
| | OPENING PROTECTIVES. |
| | |
| | 2G) PLEASE NOTE THE 701 SQUARE FEET TAKEN FOR THE NORTH |
| | WALL INCLUDES THE PARAPET. THE HEIGHT OF THE BUILDING |
| | IS TO BE TAKEN FROM FLOOR FINISH TO FLOOR FINISH OF THE |
| | NEXT STORY. FOR A SINGLE STORY BUILDING A STORY IS TO |
| | BE MEASURED FROM THE TOP OF THE FLOOR FINISH TO THE TOP |
| | OF THE CEILING JOIST OR WHERE THERE IS NOT A CEILING, |
| | TO THE TOP OF THE ROOF RAFTERS. SEE DEFINITION OF STORY |
| | CHAPTER 2OF THE 2017 FBC-B. 15.0 FT. X 40.5 FT.= 607.5 |
| | 607.5/147= 0.24 % OPENINGS. TABLE 708.5 OF THE 2017 |
| | FBC-B FOR NON-SPRINKLERED BUILDINGS ONLY ALLOWS 15 % |
| | UNPROTECTED OPENINGS. FOR EITHER PROTECTED OPENINGS OR |
| | THE BUILDING FIRE SPRINKLERED THE TABLE WOULD ALLOW 45% |
| | OPENINGS. |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. SINCE THE WALL IS BEING FILED |
| | IN THE YES YOU ARE MAKING IT BETTER BUT IT IS NOT CODE |
| | COMPLIANT. TABLE 708.5 OF THE 2017 FBC-B FOR |
| | NON-SPRINKLERED BUILDINGS ONLY ALLOWS 15 % UNPROTECTED |
| | OPENINGS. FOR EITHER PROTECTED OPENINGS OR THE BUILDING |
| | FIRE SPRINKLERED THE TABLE WOULD ALLOW 45% OPENINGS. |
| | 1ST ROUND OF COMMENTS. NORTH LINE WALL, PLEASE PROVIDE |
| | AT WHAT PERCENTAGE OF WALL OPENINGS IS PROPOSED & IN |
| | CONFORMANCE WITH TABLE 705.8. UNPROTECTED OPENINGS. |
| | |
| | 2H-2I) COMPLIED. |
| | |
| | 3)2ND REQUEST. THE WIND DESIGN CRITERIA IS GIVEN THANK |
| | YOU BUT THE ROOF PRESSURES ARE LOW ROOF ZONES 1 & 2 ARE |
| | 3 PSF LOW FOR 10 SQ. FT. AND ZONE 3 IS 3.3 PSF IF THIS |
| | WAS A B EXPOSURE FOR A C EXPOSURE FOR 15 FT. MEAN ROOF |
| | HEIGHT THE ADJUSTMENT COEFFICIENT IS 1.21. MEAN ROOF |
| | HEIGHT 15 FEET, VASD 132, TRIBUTARY AREA 10 SQ. FT. AND |
| | EXPOSURE C ZONE 1 IS -35.3, ZONE 2 -52.5 AND ZONE 3 |
| | -79.1. NO PARAPET 3 FEET HIGH OR HIGHER. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET A-3 SHOWS THE ELEVATIONS |
| | OF THE BUILDING WITH SERVICE LOADS (VASD) FOR THE |
| | COMPONENTS AND CLADDING BUT DOES NOT PROVIDE THE WIND |
| | DESIGN CRITERIA. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | |
| | 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 3.2. RISK CATEGORY. |
| | |
| | 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 4) BUILDING PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 5A) BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5B BUILDING PROVISO: ) DELEGATED ENGINEERING. |
| | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| | RECORD FOR REVIEW. |
| | |
| | 5C) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6) BUILING PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) COMPLIED. ROOFING SCUPPERS/ OVERFLOOWS NOT PART OF |
| | THIS PROJECT, ROOFING COMPLETED UNDER SEPARATE PERMIT. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |