| 2020-08-20 12:54:35 | 1) THE PLUMBING SHEETS AND ARCHITECTURAL PLANS DO NOT |
| | APPEAR HAVE A DIGITAL SIGNATURE OR SEAL IN ACCORDANCE |
| | WITH FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005. |
| | 2) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| | MOISTURE.FBC-BUILDING SEC. 1210.2.2. SHT. A-4 SHOWS |
| | THESE AREAS TO BE PAINTED DRYWALL. THIS IS NOT |
| | ACCEPTABLE AND DOES NOT COMPLY WITH THE CODE EVEN IF AN |
| | EPOXY TYPE PAINT IS USED. |
| | 3) SHT. LS-1 - "CODES" BOX - THERE IS LANGUAGE THAT |
| | REFERS TO MIAMI-DADE ADMIN. AMENDMENTS. REMOVE THIS |
| | VERBIAGE AS IT IS NOT APPLICABLE.THE CITY OF WEST PALM |
| | BEACH ADMIN. AMENDMENTS TO THE FBC HAVE BEEN ADOPTED IN |
| | THIS MUNICIPALITY. THE NOTE ALSO REFERS TO THE 2010 |
| | FLORIDA ACCESSIBILITY CODE. THE 2017 FBC-ACCESSIBILITY |
| | VOLUME IS THE CODE IN EFFECT. CORRECT THE NOTE. |
| | 4) SHT. P-1 - PLUMBING NOTES - NOTE #4 REFERS TO AIR |
| | CHAMBERS. AIR CHAMBERS ARE NOT PERMITTED. FBC-PLUMBING |
| | SEC. 604.9. |
| | 5) SHT. P-1 - PLUMBING NOTES - NOTE #10 - INSULATION |
| | INSTALLED ON THE HOT WATER LINE SHALL HAVE A MINIMUM |
| | WALL THICKNESS OF 1 INCH PER FBC-ENERGY TTABLE |
| | C403.2.10. |
| | 6) SHT. P-1 - PLUMBING NOTES - NOTE #21 - TEMPERATURE |
| | LIMITING DEVICES SHALL COMPLY WITH ASSE 1070. |
| | FBC-PLUMBING SEC.607.1.2. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |