Plan Review Notes
Plan Review Notes For Permit 20070750
Permit Number 20070750
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-20 12:54:351) THE PLUMBING SHEETS AND ARCHITECTURAL PLANS DO NOT
 APPEAR HAVE A DIGITAL SIGNATURE OR SEAL IN ACCORDANCE
 WITH FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005.
 2) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.FBC-BUILDING SEC. 1210.2.2. SHT. A-4 SHOWS
 THESE AREAS TO BE PAINTED DRYWALL. THIS IS NOT
 ACCEPTABLE AND DOES NOT COMPLY WITH THE CODE EVEN IF AN
 EPOXY TYPE PAINT IS USED.
 3) SHT. LS-1 - "CODES" BOX - THERE IS LANGUAGE THAT
 REFERS TO MIAMI-DADE ADMIN. AMENDMENTS. REMOVE THIS
 VERBIAGE AS IT IS NOT APPLICABLE.THE CITY OF WEST PALM
 BEACH ADMIN. AMENDMENTS TO THE FBC HAVE BEEN ADOPTED IN
 THIS MUNICIPALITY. THE NOTE ALSO REFERS TO THE 2010
 FLORIDA ACCESSIBILITY CODE. THE 2017 FBC-ACCESSIBILITY
 VOLUME IS THE CODE IN EFFECT. CORRECT THE NOTE.
 4) SHT. P-1 - PLUMBING NOTES - NOTE #4 REFERS TO AIR
 CHAMBERS. AIR CHAMBERS ARE NOT PERMITTED. FBC-PLUMBING
 SEC. 604.9.
 5) SHT. P-1 - PLUMBING NOTES - NOTE #10 - INSULATION
 INSTALLED ON THE HOT WATER LINE SHALL HAVE A MINIMUM
 WALL THICKNESS OF 1 INCH PER FBC-ENERGY TTABLE
 C403.2.10.
 6) SHT. P-1 - PLUMBING NOTES - NOTE #21 - TEMPERATURE
 LIMITING DEVICES SHALL COMPLY WITH ASSE 1070.
 FBC-PLUMBING SEC.607.1.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW