| 2020-09-01 16:38:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20070750 |
| | ADD: 515 CLEMATIS ST. |
| | CONT: NELSON CONSTRUCTION GC, INC. |
| | TEL: 305-331-1400 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 01/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED CONTRACT VALUE OF $185,482.00 IS FOR |
| | LABOR AND MATERIALS FOR THE PROJECT AS SEEN IN THE |
| | CONTRACT. WHAT THE CONTRACT DOES NOT INCLUDE IS THE |
| | DESIGN TEAM CONTRACT WITH THE OWNER. THIS VALUE IS ALSO |
| | TO BE INCLUDED IN THE TOTAL COST OF THE PROJECT. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 109.3* |
| | BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | 2) SHEET A-1,SITE PLAN, DEMO & LIFE SAFETY LEGEND. |
| | 2A)LAST KNOWN USE FOR THIS BUILDING? WE HAVE NO |
| | LICENSING FOR THIS BUILDING AND PALM BEACH COUNTY DOES |
| | NOT EVEN HAVE THE BACK BUILDING ON THE TAX ROLES! ONLY |
| | THE FRONT BUILDING. THE LEVEL II ALTERATION DOES NOT |
| | FIT AS WELL AS LEVEL III LIMITED STRUCTURAL |
| | ALTERATIONS. 907.4.4 OF THE EXISTING BUILDING CODE. |
| | THIS SECTION REFERS YOU BACK TO 807.5 EXIST. BUILD |
| | CODE. IT APPEARS WITH THE NOTES ON THE PLANS THE |
| | DESIGNER OF RECORD IS ALREADY TRYING TO COMPLY WITH |
| | SECTION 807.6 VOLUNTARY LATERAL FORCE RESISTING SYSTEM |
| | ALTERATIONS WITH THE ANCHORING OF THE ROOF FRAMING |
| | MEMBERS TO THE EXISTING TIE BEAM. |
| | 2B) THIS BUILDING DOES QUALIFY AS A HISTORICAL |
| | BUILDING. HISTORIC PRESERVATION HAS ALREADY C COMMENTED |
| | THAT THE EXTERIOR OF THE BUILDING IS TO STAY BLOCK NO |
| | STUCCO. PLEASE PROVIDE HOW THE BLOCK WALL WILL BE |
| | DESIGNED AND CONSTRUCTED IN SUCH A MANNER AS TO PREVENT |
| | THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY |
| | PROVIDING A WATER RESISTIVE BARRIER? 2017 FBC-B SECTION |
| | 1403.2 WEATHER PROTECTION. |
| | 2C) THE PLANS ARE SILENT AS TO WHAT EXCEPTIONS THE |
| | DESIGNER IS TAKING FOR A HISTORIC BUILDING? 107.2.1.2. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | 2D) NOTE # 8 INDICATES THE BUILDING IS 2434.05 SQ. FT. |
| | / 100 = 24.34 OCCUPANT. PLEASE NOTE IN THE 2017 FBC-B |
| | TABLE 1004.1.2 DOES DIVIDE BY AN OCCUPANT LOAD FACTOR |
| | OF 100 THE RESULT 24.34 OCCUPANTS, YOU ALWAYS ROUND UP |
| | TO THE NET WHOLE OCCUPANT, BOAFS INFORMAL |
| | INTERPRETATION AND 2015 IBC- COMMENTARY. |
| | 2E) NOTE # 9 INDICATES THE BUILDING CONSTRUCTION TYPE |
| | AS III. PLEASE PROVIDE IF THE MINIMUM BUILDING TYPE IS |
| | EITHER III-A OR III-B. TABLES 504.3, TABLE 504.4, TABLE |
| | 506.2, TABLE 601 & TABLE 602 OF THE 2017 FBC-B. TABLE |
| | 602, 0-5 FEET REQUIRES A 1 HOUR RATED WALL FOR BUSINESS |
| | OCCUPANCY. |
| | 2F) EAST PROPERTY LINE NOTE NUMBER 12 INDICATES THE |
| | CUTTING IN THE WALL A NEW EXTERIOR DOORWAY. SHEET A-2 |
| | ON THE FLOOR PLAN EAST WALL THE NEW OUTSWING DOOR IS |
| | LABELED E. PLEASE NOTE THAT DOORS & WINDOWS SHALL NOT |
| | OPEN OR PROJECT INTO THE PUBLIC RIGHT OF WAY. 3202.2 OF |
| | THE 2017 FBC-B ALSO SEE TABLE 705.8 OPENING PROECTIVES. |
| | 2G) NORTH LINE WALL, PLEASE PROVIDE AT WHAT PERCENTAGE |
| | OF WALL OPENINGS IS PROPOSED & IN CONFORMANCE WITH |
| | TABLE 705.8. UNPROTECTED OPENINGS. |
| | 2H) THE WEST WALL OF THE STRUCTURE, PLEASE PROVIDE AT |
| | WHAT PERCENTAGE OF WALL OPENINGS IS PROPOSED AND IN |
| | CONFORMANCE WITH TABLE 705.8 UNPROTECTED OPENINGS. |
| | 2I) THE SOUTH WALL OF THE STRUCTURE WILL NEED TO USE AN |
| | ASSUMED PROPERTY LINE BETWEEN STRUCTURES TO SEE WHAT |
| | PERCENTAGE OF WALL OPENINGS WILL BE IN COMPLIANCE FOR |
| | BOTH STRUCTURES. TABLE 705.8 UNPROTECTED OPENINGS. |
| | 3) SHEET A-3 SHOWS THE ELEVATIONS OF THE BUILDING WITH |
| | SERVICE LOADS (VASD) FOR THE COMPONENTS AND CLADDING |
| | BUT DOES NOT PROVIDE THE WIND DESIGN CRITERIA. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| | INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| | REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| | THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| | |
| | 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 3.2. RISK CATEGORY. |
| | |
| | 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 4) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 5A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 5C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7A) SHEET A-3 THE WEST ELEVATIONS SHOW THE OVERFLOW |
| | SCUPPERS AND COLLECTOR HEADS AS WELL AS THE SECONDARY |
| | EMERGENCY OVERFLOW DRAINS. PLEASE NOTE THAT BOTH THE |
| | OVERFLOW SCUPPERS AND SECONDARY OVERFLOW SCUPPERS ARE |
| | DEPICTED AT THE SAME HEIGHT. THE SECONDARY OVERFLOW |
| | SCUPPERS SHOULD BE IN COMPLIANCE WITH SECTION 1503.4.2 |
| | OF THE FBC-B, 2 TO 4 INCHES HIGHER THAN THE OVERFLOWS. |
| | |
| | 7B) THE SECOND ISSUE WITH THE EMERGENCY OVERFLOWS AS |
| | DRAWN IS THERE LOCATION. WHAT IS NOT VISIBLE ON THE |
| | VERTICAL PLAN IS THE CRICKETS BACK OF THE PROPOSED |
| | PARAPET. AT THE SHOWN HEIGHT THEY WILL BE BENEATH THE |
| | CRICKETS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED |
| | TO ACHIEVE CODE COMPLIANCE. |
| | |
| | 7C) THE ROOF PLAN A2 SHOWS THE ROOF SLOPING TO THE WEST |
| | AND THE PROPOSED CRICKETS. WHAT THE ROOF DRAINAGE PLAN |
| | IS MISSING IS THE RAINFALL RATE TO CALCULATE THE |
| | DRAINAGE FOR THE SCUPPERS, AND SECONDARY EMERGENCY |
| | OVERFLOW SCUPPERS. 2017 FBC-B 1503.4 ROOF DRAINAGE AND |
| | DRAIN LEADERS AND CONDUCTORS SHALL BE SIZED IN |
| | ACCORDANCE WITH 1106 AND 1107 AS APPLICABLE OF THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| | |
| | 7D) ROOF DOWN SPOUTS SHALL DISCHARGE AT LEAST 1 FOOT |
| | AWAY FROM THE STRUCTURE SIDEWALKS, WHETHER BY |
| | UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS, |
| | 2017 FBC-B 1503.7. |
| | |
| | 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2020-09-01 15:25:12 | 09/01/20 IN REVIEW. J W. |