| 2020-08-17 13:26:06 | 1) INDICATE ON THE PLANS WHICH FLOOR WILL BE RENOVATED |
| | TO COMPLY WITH THE FLORIDA BUILDING CODE-ACCESSIBILITY |
| | CODE. |
| | 2) SHT. A1.1.1 - THE LENGTH OF THE STANDARD STALLS ARE |
| | SHOWN AS 52 1/2 INCHES DEEP. THE MINIMUM DEPTH OF THE |
| | STANDARD TOILET STALLS SHALL BE 60 INCHES FOR FLOOR |
| | MOUNTED WATER CLOSETS AND 56 INCHES FOR WALL HUNG WATER |
| | CLOSETS PER FBC-PLUMBING SEC.405.3.1. |
| | 3) SHT. A1.1.1 - SHOW THE DEPTH OF THE HANDICAP |
| | ACESSIBLE TOILET STALLS. COMPLY WITH 2017 FBC - ACCESS. |
| | SEC.604.3.1. |
| | 4) SHT. A1.1.4 - SHOW THE LOCATION OF THE DRINKING |
| | FOUNTAIN ON THE ALTERNATE RESTROOM PLAN. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 5) SHT. A2.1.1 - DETAILS #1, 7,8 &9 - THE GRAB BARS |
| | SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE |
| | PER 2017 FBC- ACCESS. SEC.609.4. |
| | 6) SUBMIT A WATER AND SANITARY RISER DIAGRAM FOR THE |
| | PROPOSED CHANGES CHANGES TO SANITARY AND WATER SYSTEMS. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| | 7) SUBMIT THE TOTAL OCCUPANT LOAD FOR THIS FLOOR. |
| | REDUCTION IN THE EXISTING SANITARY FACILITIES MAY |
| | CREATE A PLUMBING CODE VIOLATION IN REGARDS TO THE |
| | MINIMUM NUMBER OF REQUIRED NUMBER PLUMBING FIXTURES PER |
| | FBC-PLUMBING TABLE 403.1. SHT. ALS 1.1 NOTES THE |
| | OCCUPANT LOAD AS 16 PERSONS. THIS DOES NOT SEEM |
| | CORRECT. PROVIDE THE SQUARE FOOTAGE OF THE FLOOR. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |